1 Introduction

Structural behaviour can be strongly affected by fire due to the decay of material properties at high temperature and the introduction of indirect actions induced by restrained thermal dilation [1]. Fortunately, concrete structures generally show a satisfactory behaviour in case of fire, owing to the low thermal diffusivity. The temperature, in fact, steeply decreases from the exposed face to the inner core, so protecting most of the section and the reinforcing bars.

In this context, explosive spalling is particularly detrimental, since the reduction of the section (due to the expulsion of shards from the exposed face) weakens the insulation capability of the concrete cover. Fire spalling consists in the sudden separation of concrete splinters from the hot surface due to the interaction between cracking and the build-up of pore pressure in the pores [2]. In particular, fracture tests on hot concrete under sustained pore pressure corroborate the idea that a combination of mechanical stress and pore pressure is generally needed for spalling [3, 4].

Generally speaking, spalling increases the overall thermal damage, this leading to higher costs for repair. Furthermore, when structural stability is a concern, it should be considered that explosive spalling can significantly speed up the decay of fire resistance due to the reduction of the bearing cross-section and the possible direct exposure of the rebars to the hot gases.

The full understanding of spalling phenomenon, and consequently its reliable prediction in the design phase, is made particularly difficult by the interaction of many different material and structural aspects [5].

During heating, thermal stress develops because of the steep thermal gradients, leading to tension in the cold core and compression in the hot layer. This latter fosters cracking parallel to the isothermal surfaces, locally reducing the mechanical stability. Other meso-scale processes can favour micro-cracking, such as strain incompatibility between matrix and aggregate [6]. On the other hand, pore pressure is responsible for the violent nature of spalling, because of its effects on the stability of cracks. Pressure development in the pores is caused by water vaporization, since vapour escape is constrained.

The kinetic of moisture migration induced by pressure gradients is very important in spalling development and it is mainly related to concrete permeability. In particular, moisture is pushed toward the cold core, where vapour condensation can occur due to the lower temperature [7]. In dense concrete (such as High-Performance Concrete—HPC) even water saturation in the pores can be attained and a region with very low permeability may form (the so-called moisture clog [8]). The formation of a saturated layer brings in two main effects: (a) increase of vapour pressure ahead moisture clog, vapour release being prevented, and (b) increase of pressure within moisture clog due to thermal dilation of liquid water (namely, liquid pressure [9]). Such aspect, together with the higher heat-sensitivity and brittleness, makes HPC more sensitive to spalling than Normal-Strength Concrete—NSC [7, 10].

Many of the studies conducted so far clearly show that spalling phenomenon can be effectively reduced, or even avoided at all, if polypropylene fibre is added to the mix, typically in the range 1–2 kg/m3 (≈ 0.1–0.2% by volume). Polypropylene fibre, in fact, melts at 160–170 °C producing voids and microcracks in the cement paste [8, 11, 12]. As a consequence, smoother moisture gradients [13] and lower pressure peaks [3] are observed, and possible relaxation of thermal stress is expected [11, 14].

Even though numerical models have been developed addressing fire spalling progression in concrete, the reliable prediction of its evolution is significantly affected by several uncertainties such as the mutual interaction between pore pressure and concrete fracture behaviour (as reported in [3, 4]), and porosity and permeability variation with temperature. This makes experimental investigation often necessary.

Tests aimed at assessing concrete sensitivity to explosive spalling can be performed on different specimen geometries under different heating and loading conditions [15].

A first group of tests is based on (small-scale) unloaded prismatic or cylindrical specimens [3, 10, 13, 16,17,18], in which temperature and/or pressure are monitored during the test. There are also examples in which external loading is applied [19,20,21].

Another set of tests is generally focused on slabs or prismatic specimens under different conditions of heating and loading. In many cases heating is applied on one face only, while external loading can be applied via active or passive systems, in one [22,23,24,25,26,27] or two directions [14, 21, 22].

A third level of investigations is represented by full-scale testing. Obviously, in assessing fire spalling sensitivity of concrete, the balance between cost and representativeness should be pursued, since cost and time burden increases with testing scale.

The common evidence is that (1) relevant spalling is unlikely in small specimens when stress is caused just by thermal gradients, (2) external compression applied during heating increases spalling probability [24, 26, 28], and (3) biaxial loading conditions are more severe than uniaxial ones [28].

In order to cast some light on the effect of fibre type in fire spalling sensitivity of HPC, an experimental campaign has been launched at Politecnico di Milano, in collaboration with the Global Product Innovation Department of Italcementi S.p.A.—HeidelbergCement Group, based on unreinforced slabs subjected to heating under biaxial loading.

The experimental investigation is based on eight slabs made of four concrete mixes (fc ≈ 60 MPa, with silico-calcareous aggregate): without fibre — reference mix — (1), with 2 kg/m3 of monofilament (2) or fibrillated (3) polypropylene fibre, or with 40 kg/m3 of steel fibre (4).

2 Mix design and test setup

Four concrete mixes differing only for fibre type have been studied. Cement type CEM I - 42.5 R has been used in combination with Ground Granulated Blast-furnace Slag (GGBS), as shown in Table 1 (see also [29, 30]).

Table 1 Mix designs and main properties of the concrete mixes

Silico-calcareous aggregate with maximum size of 16 mm has been used and the water-to-cement ratio has been designed for a target cylindrical compressive strength at 28 days fc ≈ 60 MPa. In addition to the plain mix, the other three mixes contain one of the following fibre type: 2 kg/m3 of monofilament polypropylene fibre (L = 12 mm, Øeq = 20 μm, extruded straight fibre treated with a surfactant agent) designed specifically to prevent concrete spalling [8], 2 kg/m3 of fibrillated polypropylene fibre (L = 12 mm, Øeq = 48 μm, straight fibre obtained by longitudinally cutting stripes) generally used to limit early-age shrinkage [31] or 40 kg/m3 of steel fibre (L = 35 mm, Øeq = 550 μm, hooked ends). Two slabs per mix were cast.

Spalling sensitivity has been assessed on unreinforced slabs (800 × 800 × 100 mm) subjected to Standard Fire at the bottom face under biaxial membrane compression (Fig. 1). The loading system consists in a welded steel frame restraining 8 hydraulic jacks (2 per side) with a total capacity of 1000 kN per axis. The horizontal furnace is powered by an actively-controlled propane gas torch, which is able to strictly follow the prescribed heating curve.

Fig. 1
figure 1

Concrete slab and detail of the PT sensor. PT pressure–temperature sensors;LVDT displacement transducers measuring the deflection; RL 3 rigid legs of the LVDT-holding frame

During the test, pressure and temperature have been monitored through the thickness via embedded sensors [3] placed at the distances of 10, 20, 30, 40, 50 and 60 mm from the exposed face, while the flexural behaviour has been monitored through 6 Linear Voltage Displacement Transducers (LVDTs) measuring the vertical displacements at the top cold face.

Heating is applied only to the central part (600 × 600 mm) of the slab, so to keep colder the perimeter in contact with the hydraulic jacks. The confining effect provided by such cold rim is kept as limited as possible by sixteen radial cuts aimed at interrupting its mechanical continuity. Further details on the main features of the test setup are reported in Lo Monte and Felicetti [14].

3 Results and discussion

A total of eight specimens (two per mix) was tested. Fire duration was set in the range 100–120 min in absence of spalling, otherwise heating was stopped when the slab was no more able to sustain the external biaxial compression (34–35 min). The very similar fire duration among the tests (in which spalling took place) makes it possible to compare spalling sensitivity for different concretes just in terms of onset time and final depth of spalling.

Compressive load was designed in order to instate a constant mean compressive stress in the thickness of 10 MPa aimed at preventing the onset of tensile stress.

3.1 Observed spalling

Spalling occurred in both plain concrete slabs (first very severe event after 19 and 34 min for slab A and B, respectively) and only in one case for steel fibre-reinforced concrete (first very severe event after 35 min in slab B). It is worth noting that, in all the three cases, first spalling occurred in a very violent way involving all the heated area. Only for slab A of mix M70S (plain concrete), test could be continued after the first spalling event, showing many following minor events, each one taking place in smaller but significant parts of the heated area (up to about 30% [32]) till the end of heating (35 min). The final spalling depth was comparable among the three specimens and the spalled layer appeared rather homogeneous in the heated area. The spalled profile was measured after the test via laser profilometry, as described in Lo Monte and Felicetti [14], in order to evaluate both maximum and average depths. The moisture front was also measured in one slab only via Ground-Penetrating Radar technique (see [33]).

The regularity of the spalled surface is a very interesting outcome, since it can be inferred that, in substantially uniform heating and loading conditions, the size of spalled splinters is not strictly related to local mechanisms at concrete meso-scale (such as aggregate-to-cement paste interaction). In polypropylene fibre concretes, spalling did not occur and just light scaling was observed at the end of heating. Pictures of some specimens after testing are reported in Fig. 2, while the results are summarized in Table 2.

Fig. 2
figure 2

Bottom heated face of three specimens after testing and scheme of fracturing process in (a) plain, (b) steel and (c) polypropylene fibre concrete slabs

Table 2 Summary of tests and results

In Fig. 2 spalling development is sketched on the basis of the observation of concrete debris after testing. In plain concrete, detachments took place probably due to the formation of cracks triggered by compressive thermal stress parallel to the hot face. Pore pressure favoured the unstable propagation of fractures, fostering the violent expulsion of delaminated layers (Fig. 2a). Such mechanisms were partly constrained in steel fibre-reinforced concrete due to the bridging effect provided by steel fibres crossing the cracks. This bridging effect was probably sufficient in slab A of M70S SF40, since spalling did not occur. On the other hand, the bridging effect of steel fibre was nullified in slab B by the formation of a “pulverized” band of 15–20 mm thickness, in which concrete was disrupted in the spalling event in powder-like debris (Fig. 2b). The thickness of this layer was assessed by vacuum cleaning the furnace after the test, followed by sieving and weighing of the debris. Moreover, fibres longer than half of their length were protruding from both the remaining slab and the coarse concrete chunks spalled ahead the pulverized band. By cutting and weighing the projecting filaments, an average length of 21 mm was assessed, namely 60% of the fibre length (while 25% would be expected in case of pulled out randomly distributed fibre).

It is worth noting that the average thickness of the first spalled layer was about 10, 18 and 23 mm in slabs M70S_A, M70S_B and M70S SF40_B, respectively. The correspondent temperatures at the fracture plane at the onset of the first spalling event (19, 35 and 34 min, respectively) are within a very narrow range (225–246°C).

It should be noted that with more severe heating rates and/or thicker specimens (in which thermal stress is higher due to the increased flexural stiffness) spalling can take place also at the very beginning of the test due to the development of higher self-stress.

3.2 Temperature and pore pressure development

In Fig. 3 temperature of furnace, hot and cold faces of the slab, and at the 6 internal measurement points (10, 20, 30, 40, 50 and 60 mm from the heated face) is shown for three specimens, namely plain (M70S_B), steel (M70S SF40_B) and monofilament polypropylene (M70S PM2_B) fibre concrete slabs. Temperature in fibrillated polypropylene fibre concrete (M70S PF2) is not shown, since it is very similar to monofilament polypropylene fibre concrete (M70S PM2). Temperature curves in M70S_B and M70S SF40_B are reported only up to the end of heating (about 34–35 min).

Fig. 3
figure 3

Plots of temperature of oven, hot and cold faces, and at 6 depths for three slabs, as a function of time. (^Temperature at 0 mm was not directly measured, but analytically evaluated)

Looking at temperature development, no direct effect of fibre can be recognized, since no particular trend can be clearly identified by comparing the specimens. Though this might have been expected in case of steel fibre, given the little influence on thermal diffusivity [34], it is also confirmed that the mass transport enhancement allowed by polymeric fibre has little effects on the thermal field.

Pore pressure monitoring along slab thickness is very helpful in understanding the role played by fibre type, especially in case of polypropylene fibre, whose beneficial effects mainly consist in increasing concrete permeability and consequently reducing pore pressure.

Pressure development is reported as a function of time in Fig. 4, where it is clear that the highest values of peak pressure have been reached in the case of steel fibre-reinforced concrete, even higher than in plain concrete.

Fig. 4
figure 4

Plots of pressure at 6 depths for one slab per mix, as a function of time

This can be probably ascribed to the stabilizing effect of steel fibre on crack propagation and, then, on the damage-induced permeability. Such evidence casts some doubt on the use of steel fibre alone for limiting spalling, since the benefits in terms of enhanced mechanical properties may be overcome by the higher pore pressure developed during fire exposure.

The lowest values of pressure have been achieved in the mix with monofilament polypropylene fibre, while slightly higher values have been observed in the case of fibrillated polypropylene fibre. This evidence has been already observed in Lo Monte et al. [4] and can be ascribed to a higher effectiveness of monofilament fibre in increasing concrete permeability, thanks to a higher dispersion in the matrix with respect to fibrillated fibre.

Experimental pressure profiles for different values of fire duration are plotted in Fig. 5a for the reference mix (namely, plain concrete slab B—M70S_B) and for monofilament polypropylene fibre concrete (slab B, M70S PM2_B). Initially, the development of pressure is rather similar, since polypropylene fibres in the hygrally-active region (where significant pressures develop) are not melted yet. After 20 min of heating, when temperature in the hottest 20 mm of the slab is higher than the melting temperature of polypropylene (about 160–170 °C), the difference between the two mixes becomes evident. In particular pressure quickly rises in plain concrete at 10 mm from the heated face, leading to relevant pressure gradients. On the other hand, in polypropylene fibre concrete, pressure remains limited and the gradient is far smoother. Moreover, in this latter case the pressure peak tends to follow the fibre melting front and then it is significantly deeper than in plain concrete.

Fig. 5
figure 5

a Pressure profiles at different fire durations in plain (M70S_B) and monofilament polypropylene fibre (M70S PM2_B) concrete slabs, b vertical displacement at the midpoint of four specimens, and c, d pressure versus temperature in fibrillated polypropylene fibre concrete slabs M70S PF2_A and M70S PF2_B for an applied membrane stress of 10 and 5 MPa, respectively

Steel fibre-reinforced concrete behaved very similarly to plain concrete, with pressure profiles characterized by even sharper gradients. This is reasonably caused by the lower hot permeability (with respect to polypropylene fibre concrete), which limits vapour release, thus forcing pressure to remain concentrated in the hot layer.

In Fig. 5c, d, pressure is reported as a function of temperature, for the two slabs of mix M70S PF2 (fibrillated polypropylene fibre concrete), together with the saturation vapour pressure curve, PSV.

It is worth noting that slab B was subjected to a biaxial membrane compression of 5 MPa, while all the other specimens were tested with 10 MPa. Looking at the results, it clearly appears that for growing depths, pressure–temperature rate rises (pressure–temperature curve are closer to the saturation vapour pressure curve), and this trend has been observed in all the tests. This is reasonably caused by the increase of the distance with respect to the heated face, from which vapour can be released. Furthermore, it can be observed that pressure–temperature rates and pressure peaks are higher for an external membrane compression of 5 MPa (Fig. 5d) compared to 10 MPa (Fig. 5c), so highlighting the role of external load.

Such result can be explained looking at the numerical analyses reported in Lo Monte and Felicetti [14], which aimed at simulating the experimental test at issue. In particular, it was shown as an external membrane compression of 5 MPa is sufficient to avoid any tensile stress (and, consequently, any crack) in the concrete core because of thermal strain. This means that no significant difference is expected in terms of permeability in the slab core, when the external compression is increased from 5 to 10 MPa. On the other hand, the increase of the external compression leads to a more pronounced damage in the hot layer, which is already compressed due to thermal stress. This increased damage, which implies higher cracking and permeability, fostering vapour release and pore pressure reduction. For this reason, higher pore pressure was reached for a confining stress of 5 MPa.

It is important to underline that, for lower values of compressive load, the trend is expected to be the opposite. Decreasing the external compression, in fact, tensile stress arises in the specimen core and tensile strength can be attained. In such case, cracking occurs and pore pressure release takes place. This means the maximum pressure peaks should be expected for intermediate values of external compression.

Spalling risk and severity, however, should continuously increase with the external load, due to the higher overall damage in the hot layers, as reported in Lo Monte and Felicetti [14] and Miah et al. [28].

3.3 Flexural behaviour

The vertical mid-span displacement is shown in Fig. 5b for one slab per mix for the whole fire duration. It is possible to notice that the flexural behaviour can be divided into two stages. In the first phase of heating, sagging deflection takes place because of the thermal dilation of the bottom heated face. Afterwards, when the decay of concrete stiffness in the hot layer becomes sizable, hogging deflection occurs due to the rise of the stiffness centre, which translates into a negative eccentricity for the external load (constantly applied at the mid-plane). Thus, in the second phase, the displacement rate changes sign (after about 25–30 min of fire duration). Obviously, hogging deflection during heating can occur only if a significant external load is applied.

Looking at Fig. 5b, no remarkable difference can be observed between plain and steel fibre-reinforced concrete, while if monofilament or fibrillated polypropylene fibre is added, hogging deflection occurs significantly earlier.

In particular, the maximum sagging deflection is 700–800 μm for plain and steel fibre-reinforced concretes, while is 400–500 μm in the case of polypropylene fibre concretes. This result implies that polypropylene fibre leads to a more pronounced increase of concrete deformability with temperature, so fostering the effect of the external load (hogging deflection).

The concretes at issue have been extensively studied in a previous experimental campaign focused on the compressive behaviour of concrete cylinders at high temperature and in residual conditions, proving that the decay of elastic modulus as a function of temperature is just slightly influenced by the addition of polypropylene fibre [35, 36]. This suggests that the difference in the flexural behaviour is probably caused by a higher transient thermal strain occurring when polypropylene fibre is added (as observed also in [11]).

4 Conclusions

A novel experimental setup for investigating fire spalling phenomenon in concrete has been designed at Politecnico di Milano based on slabs heated at the bottom, while subjected to external biaxial membrane compression.

Taking advantage of this facility, the goal of the presented experimental research is to study the main effects brought in by fibre type in concrete sensitivity to spalling. To this aim, four mixes have been designed, consisting in High-Performance Concretes (fc ≈ 60 MPa, with silico-calcareous aggregate) differing only for the presence of monofilament or fibrillated polypropylene, or steel fibres. Two slabs per mix were cast.

Spalling occurred in both plain concrete slabs, and in one of the two steel fibre-reinforced specimens, while the addition of polypropylene—either monofilament or fibrillated—fibre allowed to avoid any detachment for the whole fire duration (100–120 min).

The spalling process started in all the cases with a very violent event involving all the heated area. After cooling, the spalled layer appeared rather homogeneous, corroborating the idea that, in substantially uniform heating and loading conditions, spalling phenomenon is not strictly related to local mechanisms regarding aggregate-to-cement paste interaction and that a more general explanation can be given based on temperature, pressure and stress fields.

The development of the thermal field was rather similar among the specimens. This evidence suggests a limited role played by moisture transport phenomena in concrete thermal behaviour. (Polypropylene fibre concretes have higher permeability than plain concrete due to fibre, but similar thermal diffusivity). Moreover, steel fibres are known to not significantly influence concrete thermal conductivity.

The highest values of peak pressure were reached in steel fibre-reinforced concrete, even higher than in plain concrete, probably because of a more stable crack propagation. This evidence should discourage the use of steel fibre alone with the aim of reducing spalling risk, since the induced increase in pore pressure can even offset the advantage brought in by the improved tensile toughness. In the case at hand, the beneficial effect of steel fibre was nullified by the formation of a pulverized band of concrete, which zeroed any bridging effect of the fibres anchored in the band.

On the other hand, far lower values of pressure have been observed in polypropylene fibre concrete, thanks to the increase of permeability allowed by fibre melting. In particular monofilament polypropylene fibre proved to be more effective than fibrillated polypropylene fibre in reducing pore pressure.

Plain and steel fibre-reinforced concretes experienced pressure profiles characterized by sharper gradients, reasonably due to their lower permeability, this limiting vapour release and forcing the pressure to remain concentrated in the hot layer.

As regards the mechanical behaviour, monitoring the out-of-plane deflection revealed as the introduction of polypropylene fibre probably leads to higher transient thermal strain compared to plain or steel fibre-reinforced concrete (this possibly smoothing down thermal stress).