Abstract
The article briefly states the current development of evaporative cooling generator and its advantages comparing with generators of traditional cooling. Vertical evaporative cooling generator, which adopts Close-Loop-Self-Cycle with no-pump and free convection boil in the hollow stator bar, is one of the great developments in generator design. This article emphasizes the importance of cooling system in generator; expatiates the circulation theory in two aspects, energy and flow; and analyzes the essential reason, motivity and stability of Close-Loop-Self-Cycle. The article points out that the motivity of the circulation is the heat absorbed by coolant. After absorbing heat the coolant will have the ability of doing work because of the phase change. In another words, it is the buoyancy causing by density difference leads to the Close-Loop-Self-Cycle. This conclusion is validated by experimental data.
Similar content being viewed by others
References
Ding S N. Heat and Cool of the Large Generator (in Chinese). Beijing: Science Press, 1992
Gu G B, Tian X D. The development of inner cooling technique in hydro-generator. Electric Machines and Control (in Chinese), 1997, 1(1): 46–53
Gu G B. Development and application of evaporation-cooling technology. China Electrical Equipment Industry (in Chinese), 2003, 1: 5
Xiong N. Main tasks for research and practice of evaporation-cooling technology. Advanced Technology of Electrical Engineering and Energy (in Chinese), 2000, 19(3): 36–40
Author information
Authors and Affiliations
Corresponding author
Rights and permissions
About this article
Cite this article
Yu, S., Cai, J., Guo, C. et al. Study of the circulation theory of the cooling system in vertical evaporative cooling generator. SCI CHINA SER E 49, 358–364 (2006). https://doi.org/10.1007/s11431-006-0358-1
Received:
Accepted:
Issue Date:
DOI: https://doi.org/10.1007/s11431-006-0358-1