1 Occupants’ Comfort and Energy

A significant share of the energy consumed by buildings is intended for delivering proper indoor conditions for most of its occupants. These proper indoor conditions are generally referred as comfort conditions, which have been defined by ASHRAE 55 as “…condition of mind which expresses satisfaction with the environment….” Therefore, it encompasses different components, namely thermal, visual, acoustic, air quality, layout distribution, and others.

The indoor environment depends on the combination of various physical parameters, and hence, multiple plant systems are needed for managing all of them in parallel. Most of the plant systems have a dynamic operation, with the intention of properly handle the physical parameter variations, generated by mutable weather conditions during the building lifetime. To do so, there must be a performance criterium, or criteria, to rate the efficiency of the processes carried out by the system and to trigger an intervention when the goals set are not met.

As the closest element to the exterior, the building envelope is the most influential building system for providing well-being indoors, and in particular the transparent portion (defined as the quickest path for heat, light, sound, and pollution transfer). Additional shading devices have been employed to increase the dynamism and performance of the envelope, boosting the façade composition. The adequacy of the design, functional model, and control logic would depend on the type of activity held indoors, but most importantly the type of occupants hosted.

Not all occupants perceived similarly and prefer, require, or demand the same indoor environmental conditions. Thus, depending on what the designers’ choice is:

  • The building could perform badly if a manual control has been envisaged without any correction or adaption (Masoso and Grobler 2010).

  • An autonomous building could not provide enough satisfaction, if the performance criteria are not adjusted to the occupants’ requirements, and they would feel underrated if no sense of control is given (Belafi et al. 2017; Langevin et al. 2015).

  • An adaptive building could operate decently in a mixed-mode, allowing occupants’ interaction and overriding the initially set activation thresholds (Gunay et al. 2014).

The type of operation affects the energy consumption of the building (i.e., environmental gains) and the frequency of activation, hence the fatigue on the materials, and the maintenance activities. Further replacement, or maintenance, interventions would enlarge the embodied energy of the system threatening its circular economy.

2 Shading Requirement

Taking into consideration only the lighting requirement for reading and writing activities, sufficient illuminance shall be provided under daylighting (when available) and artificial lighting. Starting from the minimum threshold established of 300 lx and a maximum of 1000 lx (following sDA and ASE lower and upper limits established by LEED v4 (2014)) to avoid the risk of glare and modifying it according to the needs of the occupant (i.e., aged eye, protected eye, and younger eye); see Table 1.

Table 1 Frequency hours of shading and lighting activation according to the lower and upper illuminance thresholds

Shading requirement has been set as the need for a lower/higher glass transmittance of the transparent portion of the building façade to regulate the daylight influx, and this would only be used when the values obtained indoors do not comply with the settings set. However, these settings were diversified to encompass a more realistic preference of different building users, and also to cover what the design regulations do not clarify: maximum illuminance values (i.e., there are only lower thresholds).

An office space (2.95 × 5.10 × 3.17 m) in Milan, Italy (45° 28′ 47″N; 9° 13′ 47″E), with 30% window-to-wall ratio (WWR) oriented toward South, was used as a case study, in which the illuminance was computed at an analysis grid at 0.8 m from the floor. The optical properties of the materials were the following: glass τvis = 0.65; ceiling ρvis = 0.8; internal walls ρvis = 0.5; and floor ρvis = 0.4.

The obtained values for different criteria were confronted against the traditional Eh evaluation; that is, what was found from analyzing preferences of a qualitative survey applied to bachelor students and what has been suggested by Turner and Mainster (2008) due to the eyesight decay. The frequency of activation and the variances obtained due to these values have been collected and presented in Table 1, additionally in Figs. 1a and 2 annual heat maps have been included to see the behavior of illuminance and required activation during the year.

Fig. 1
figure 1

Average room surface illuminance value along the year (a) and shading cycle occurrence cumulative sum throughout 3 months (i.e., summer June–Aug (s) and winter Jan–Mar (w)) for normal considerations (n), young (y), older (o), and glasses worn occupants (b)

Fig. 2
figure 2

Activation controls for artificial lighting (value 0), for shading (value 1) and no activation required (value 0.5). For a normal consideration, b younger occupants, c older occupants, and d glass worn occupants

2.1 Frequency of Use

The frequency of use of both shading and lighting appliances has been estimated from an annual simulation using the validated ray-tracing software radiance presented by Ward and Shakespeare (1998). It has been assumed that the values reported in Table 1 are a hypothetical ideal case in which the shadings are correctly operated by the building, and in which they have been adapted to a more realistic hosted occupancy type.

3 Conclusions

The need for clarifying the type of occupancy indoors is clear, as the variance of the activation hours of the electrical appliances and/or shading can reach a difference of ~13% generating a much larger quantity of cycles that could reduce the life expectancy of the building systems. Moreover, the hours of comfort have a well significant difference when considering one range or the other, for instance, for occupants wearing glasses the number of hours in which no intervention was required was ~15%; meanwhile for the established benchmark (i.e., between 300 and 1000 lx), it was ~27%. In terms of cycles, it is clear how the number of activations varies from one occupancy type to the other, given what is shown in Fig. 1b. For summer, the amount of cycles is reduced as they are mainly ON; meanwhile for the winter, a higher variance is noted due to lower daylighting availability and the perpendicularity of the light influx.

Further studies are foreseen to establish a more reliable visual comfort range for the horizontal illuminance that would allow to improve the building design. Additional surveys on diverse occupant samples are expected to assess different influential physical features.