Abstract
In power transformers with split type two secondary windings, non-symmetrical configurations are possible. The design of these transformers considers two low voltage windings mounted one on top of the other and the regulating and high voltage windings divided in two parallels. Due to the specific design of these transformers, circulating currents can exist in parallels of the high voltage and regulating windings. These currents can affect the load losses inside the transformer as more parts of the winding are energized than in the symmetrical configuration. Moreover, they may affect the design of the winding itself since the amplitudes of these circulating currents can be significant and therefore have to be taken into account during the design phase.
It is possible to calculate these currents using the finite element method (FEM) software in order to check if their values exceed the design values and to more accurately calculate the load losses of the transformers. In this paper, the results of the 3D FEM calculation of such power transformers are shown and compared with the measurement results in terms of circulating currents amplitudes in high voltage and regulation windings parallel parts. Additionally, a comparison between calculated and measured load losses is given.
Access this chapter
Tax calculation will be finalised at checkout
Purchases are for personal use only
References
Kumbhar, G.B., Kulkarni, S.V.: Analysis of short-circuit performance of split-winding transformer using coupled field-circuit approach. IEEE Trans. Power Deliv. 22(2), 936–943 (2007)
Mentor Graphics: MagNet (2017)
Koppikar, D.A., Kulkarni, S.V., Ghosh, G., Ainapure, S.M., Bhavsar, J.S.: Circulating-current loss in transfromer windings. IEE Proc.-Sci. Measur. Technol. 145(4), 2–6 (1998)
Isaka, S., Tokumasu, T., Kondo, K.: Finite element analysis of eddy currents in transformer parallel conductors. IEEE Trans. Power Appar. Syst. PAS-104(10), 2730–2737 (1985)
Pern, J., Yeh, S.: Calculating the current distribution in power transformer windings using finite element analysis with circuit constraints. IEE Proc.-Sci. Measur. Technol. 142(3), 231–236 (1995)
Fukumoto, H., Furukawa, T., Itoh, H., Ohchi, M.: Calculating leakage reactance of 9-winding transformer using time-dependent 3D FEM analysis. In: IECON 2015-41st Annual Conference of the IEEE Industrial Electronics Society, pp. 4459–4464 (2015)
Stuchl, P., Doležal, I., Zajic, A., Hruza, J., Weinberg, O.: Performance of transformers with split winding under nonstandard operation conditions. CIGRE Bien Session Paris, France (2000)
Author information
Authors and Affiliations
Corresponding author
Editor information
Editors and Affiliations
Rights and permissions
Copyright information
© 2020 Springer Nature Switzerland AG
About this paper
Cite this paper
Jurišić, B., Župan, T., Štrac, L. (2020). Calculation of Circulating Current Inside Power Transformers in Non-symmetrical Configurations. In: Németh, B. (eds) Proceedings of the 21st International Symposium on High Voltage Engineering. ISH 2019. Lecture Notes in Electrical Engineering, vol 598. Springer, Cham. https://doi.org/10.1007/978-3-030-31676-1_7
Download citation
DOI: https://doi.org/10.1007/978-3-030-31676-1_7
Published:
Publisher Name: Springer, Cham
Print ISBN: 978-3-030-31675-4
Online ISBN: 978-3-030-31676-1
eBook Packages: EngineeringEngineering (R0)