Advertisement

Implementation of Protection and Control Systems in the Transmission SS 110/10(20)/10 kV Using IEC 61850 GOOSE Messages

  • Adnan CokićEmail author
  • Admir Čeljo
Conference paper
Part of the Lecture Notes in Networks and Systems book series (LNNS, volume 59)

Abstract

This article describes implementation concept of modern protection and control system in the substation Sarajevo 13 with special reference on using IEC 61850 GOOSE messages for interlocking conditions and protection functions design. Interlocking condition of existing 110 kV gas insulated switchgear has been made by a wire on the GIS local command cabinets’ level. For proper control from P&C cabinets and local/remote SCADA level it was necessary to duplicate the interlocking conditions using IEC 61850 GOOSE messages and to protect the system in communication loss case. The 10 kV switchgear is classic air insulated medium voltage switchgear. The reverse interlocking and busbar protection are implemented by blocking high-set current stage I>> on transformer and coupling bays with pickup of high-set current stage I>> on feeder bays. The signal is transmitted via IEC 61850 GOOSE message. This article describes details for correct parameter settings of high-set current stage I>> in entire 10 kV switchgear considering predicable time delay of IEC 61850 GOOSE message because of Ethernet network. Also the IEC 61850 GOOSE messages are used for implementation of arc protection function in 10 kV switchgear.

References

  1. 1.
    Jurišić, G.: The influence of the IEC 61850 standard on protection and control systems, 11. HRO CIGRE Cavtat, no. 20130004, p. 7, November 2013Google Scholar
  2. 2.
    Vidović, F., Leci, G., Vukić, I., Ožanić, D.: Protocol IEC 61850 – proposal of the technical solution for the secondary system of distribution transformer station 1. CIRED Šibenik, p. 6, 18–21 May 2008Google Scholar
  3. 3.
    Siemens: Efficient Energy Automation with the IEC 61850 Standard Application Examples, Siemens AG Energy Sector, p. 48 (2010)Google Scholar
  4. 4.
    IEC 61850-5: Communication networks and systems in substations – Part 5: Communication requirements for functions and device models, p. 138Google Scholar
  5. 5.
    Brand, K.-P., Janssen, M.: The specification of IEC 61850 based substation automation systems, p. 52. DistribuTech (2005)Google Scholar
  6. 6.
    Higgins, N., Vyatkin, V., Nair, N.K.: Distributed power system automation with IEC 61850, IEC 61499, and intelligent control. IEEE Trans. Syst. Man Cybern. Part C (Appli. Rev.) 41(1), 81–92 (2011)Google Scholar
  7. 7.
    IEC TR 61850-1: Communication networks and systems in substations – Part 1: Introduction and overview, p. 44 (2013)Google Scholar

Copyright information

© Springer Nature Switzerland AG 2019

Authors and Affiliations

  1. 1.CET Energy Ltd.SarajevoBosnia and Herzegovina
  2. 2.Elektroprenos – Elektroprijenos BiH a.d. Banja LukaBanja LukaBosnia and Herzegovina

Personalised recommendations