Abstract
This article describes implementation concept of modern protection and control system in the substation Sarajevo 13 with special reference on using IEC 61850 GOOSE messages for interlocking conditions and protection functions design. Interlocking condition of existing 110 kV gas insulated switchgear has been made by a wire on the GIS local command cabinets’ level. For proper control from P&C cabinets and local/remote SCADA level it was necessary to duplicate the interlocking conditions using IEC 61850 GOOSE messages and to protect the system in communication loss case. The 10 kV switchgear is classic air insulated medium voltage switchgear. The reverse interlocking and busbar protection are implemented by blocking high-set current stage I>> on transformer and coupling bays with pickup of high-set current stage I>> on feeder bays. The signal is transmitted via IEC 61850 GOOSE message. This article describes details for correct parameter settings of high-set current stage I>> in entire 10 kV switchgear considering predicable time delay of IEC 61850 GOOSE message because of Ethernet network. Also the IEC 61850 GOOSE messages are used for implementation of arc protection function in 10 kV switchgear.
Access this chapter
Tax calculation will be finalised at checkout
Purchases are for personal use only
References
Jurišić, G.: The influence of the IEC 61850 standard on protection and control systems, 11. HRO CIGRE Cavtat, no. 20130004, p. 7, November 2013
Vidović, F., Leci, G., Vukić, I., Ožanić, D.: Protocol IEC 61850 – proposal of the technical solution for the secondary system of distribution transformer station 1. CIRED Šibenik, p. 6, 18–21 May 2008
Siemens: Efficient Energy Automation with the IEC 61850 Standard Application Examples, Siemens AG Energy Sector, p. 48 (2010)
IEC 61850-5: Communication networks and systems in substations – Part 5: Communication requirements for functions and device models, p. 138
Brand, K.-P., Janssen, M.: The specification of IEC 61850 based substation automation systems, p. 52. DistribuTech (2005)
Higgins, N., Vyatkin, V., Nair, N.K.: Distributed power system automation with IEC 61850, IEC 61499, and intelligent control. IEEE Trans. Syst. Man Cybern. Part C (Appli. Rev.) 41(1), 81–92 (2011)
IEC TR 61850-1: Communication networks and systems in substations – Part 1: Introduction and overview, p. 44 (2013)
Author information
Authors and Affiliations
Corresponding author
Editor information
Editors and Affiliations
Rights and permissions
Copyright information
© 2019 Springer Nature Switzerland AG
About this paper
Cite this paper
Cokić, A., Čeljo, A. (2019). Implementation of Protection and Control Systems in the Transmission SS 110/10(20)/10 kV Using IEC 61850 GOOSE Messages. In: Avdaković, S. (eds) Advanced Technologies, Systems, and Applications III. IAT 2018. Lecture Notes in Networks and Systems, vol 59. Springer, Cham. https://doi.org/10.1007/978-3-030-02574-8_19
Download citation
DOI: https://doi.org/10.1007/978-3-030-02574-8_19
Published:
Publisher Name: Springer, Cham
Print ISBN: 978-3-030-02573-1
Online ISBN: 978-3-030-02574-8
eBook Packages: Intelligent Technologies and RoboticsIntelligent Technologies and Robotics (R0)