Abstract
H. OKUBO: In the case of SF6 GIS, particle movement is not of interest under AC voltage application because the breakdown occurs just under the impulse voltage application condition. However, for a pure N2 or for small content SF6 in N2 GIS, AC breakdown would occur just under the condition of particle standing on the tank. In this case, I think that we need to change the testing method of the GIS. What do you think about it?