Abstract

Fire ignition frequency is the first quantitative measure of fire risk. Different models have been employed by the industry to estimate the frequency of fire occurrence at different locations within a plant. Earlier models provided frequencies by building type (e.g., auxiliary building and turbine building) and specific rooms (e.g., control room and cable spreading room). In the later models, fire ignition frequencies were estimated by equipment type. As fire event database expanded, a combined model was developed that combined location specific information with equipment type. In the Fire Risk Requantification Study, the latter model was further enhanced in terms of combined categories of location and equipment type and enhanced use of the information provided in event reports of the underlying database. Two-stage Bayesian approach was used to characterize the plant-to-plant variability uncertainties in the fire ignition frequencies and facilitate incorporation of plant specific information.

Keywords

Fire Risk Uncertainty Distribution Fire Occurrence Ignition Source Electric Power Research Institute 
These keywords were added by machine and not by the authors. This process is experimental and the keywords may be updated as the learning algorithm improves.

Preview

Unable to display preview. Download preview PDF.

Unable to display preview. Download preview PDF.

References

  1. 1.
    Apostolakis, G., M. Kazarians, “The Frequency of Fire in Light Water Reactor Compartments,” American Nuclear Society/European Nuclear Society Topical Meeting on Thermal Reactor Safety, Knoxville, Tennessee, April 6-9, 1980.Google Scholar
  2. 2.
    Kazarians, M., and G. Apostolakis, “Modeling Rare Events: The Frequencies of Fires in Nuclear Power Plants,” presented at the Workshop on Low Probability/High Consequence Risk Analysis, Arlington, Virginia, June 15-17, 1982.Google Scholar
  3. 3.
    “Fire-Induced Vulnerability Evaluation (FIVE)” Electric Power Research Institute EPRI-TR 100370, September 1993.Google Scholar
  4. 4.
    “Fire Events Database and Generic Ignition Frequency Model for U.S. Nuclear Power Plants”, Electric Power Research Institute EPRI-TR 1003111, November 2001.Google Scholar
  5. 5.
    S. Kaplan, “On a ‘Two-Stage’ Bayesian Procedure for Determining Failure Rates from Experiential Data,” IEEE Transactions on Power Apparatus and Systems, Volume PAS-102, 1983, pp. 195–202.CrossRefGoogle Scholar

Copyright information

© Springer-Verlag London 2004

Authors and Affiliations

  • Mardy Kazarians
    • 1
  • Francisco Joglar
    • 2
  • Steve P. Nowlen
    • 3
  • Bijan Najafi
    • 4
  1. 1.Kazarians & Associates, Inc.GlendaleUSA
  2. 2.SAICRestonUSA
  3. 3.Sandia National LaboratoriesAlbuquerqueUSA
  4. 4.SAICSan JoseUSA

Personalised recommendations