1 Introduction

Evaluation of concrete quality up to the depth of concrete cover is necessary for proper maintenance of reinforced concrete structures. One of the employed methods to analyze the existing concrete performance is the compressive strength. However, compressive strength alone cannot be an indicator for mass transfer resistance of concrete. Permeability of concrete is a major indicator of its performance in terms of durability. Carbon dioxide, chloride ion and water ingress are the primary cause of detrimental effects in concrete. Their penetration into concrete is governed by the pore structure. Hence air permeability and water permeability can be indicators for the magnitude of penetration of carbon dioxide or chloride ion. Air permeability is said to be highly correlated with porosity and pore size distribution of concrete and can be used as a measure of porosity and pore connectivity (Halamickova et al. 1995; Sugiyama et al. 1996; Abbas et al. 1999). Air permeability coefficient has high correlation with neutralization progress, water cement ratio, cement type and curing conditions (Basheer et al. 2001; Hui-sheng et al. 2009; Hamami et al. 2012).

Studies on air permeability and its relation to chloride diffusion are few and rather complicated. It is reported that chloride ion diffusion coefficient has a possibility of greatly varying between salt immersion test and in actual concrete structure. Due to such variations, evaluation of penetration of chloride ion into actual concrete structure should be considered for safer structures (Yamaji 2014). Diffusion coefficient is time dependent and decreases over time (Halamickova et al. 1995; Luping and Gulikers 2007; Pack et al. 2010; Al-alaily and Hassan 2016). This makes it difficult to evaluate chloride ion penetration into concrete by various methods. However, long-term resistance to chloride ion penetration is unclear. Since, supplementary cementitious materials like fly ash and Portland blast furnace cement are excellent in resistance to chloride ion penetration (Osborne 1999; Thomas and Bamforth 1999; McCarthy and Dhir 2005; Berndt 2009), studies on their relation between air permeability and chloride diffusion is important.

In case of air permeability, factors affecting measurement are pore structure and moisture content in concrete. On the other hand, it is considered that penetration of chloride ion into concrete is governed by the capillary absorption, permeability and diffusion by concentration gradient depending on several factors and each has its own testing methods (Basheer et al. 2001). In the electrophoretic test method (chloride ion migration test) for evaluation of chloride ion penetration, concrete specimen is subjected to water saturated condition. The main factor affecting the chloride ion diffusion coefficient by electrophoretic test (here-in-after referred as “De”) is hence the pore structure in concrete (Halamickova et al. 1995; Papadakis 2000; Yang 2006; Saeki et al. 2006) without any effect of the capillarity and permeability. Hence, air permeability coefficient can be possibly used to evaluate De. Also, assessment of chloride diffusion by electrophoretic test has its own drawbacks owing to complexity and time consumption (Truc et al. 2000) and it often overestimates the diffusion value (Luping and Gulikers 2007). But a high correlation of air permeability with De provides a scope for indirect estimation of apparent diffusion coefficient by salt immersion test (here-in-after referred as “Da”).

All the facts put together, present study aims at evaluating mass transfer resistance performance of concrete by measurement of air permeability. The correlation between air permeability and other durability indicators were examined for possible application of air permeability as a durability indicator on a wide range of conditions. Since Da can be estimated from De using established equations, a good correlation between air permeability and De facilitates easy estimation of Da. Hence, the study aims to find the correlation between air permeability and De. This provides an indirect estimation of chloride diffusion coefficient by air permeability. The relation between air permeability and neutralization, chloride diffusion by salt immersion test, porosity, cement types and curing conditions have been studied extensively. However, there are no substantial reports on correlation between air permeability and chloride diffusion coefficient by electrophoretic test especially for both laboratory tests and actual marine structures.

Laboratory tests to determine neutralization coefficient, chloride diffusion coefficient by electrophoretic test of chloride ion (De), apparent diffusion coefficient by salt immersion test (Da) and air permeability were employed. Concrete structure at sea condition for 23 years made by using fly ash and Portland blast furnace cement were also examined for penetration of chloride ion. The relation between air permeability and chloride diffusion in concrete exposed to marine conditions was also analyzed. In particular, measurement of Da and De in actual marine environment, at deeper sections of concrete cores where chloride ions not penetrated was also performed.

2 Materials and Method

Broadly, experimental investigations were carried out for laboratory prepared concrete and concrete cores obtained from concrete structure exposed to actual marine conditions for as long as 23 years. The experimental procedure for each is explained.

2.1 Laboratory Prepared Concrete

Three types of concrete were prepared with Ordinary Portland cement (“N”), type B-blast furnace slag cement (“BFSC”) and fly ash as admixture (cement replacement). The properties of materials used are shown in Table 1. Three water to binder ratios (“W/B”), 45, 55, 65% were employed (Table 2, all materials in kg/m3). OPC, FAC and BBC are concretes made with Ordinary Portland cement (“N”), type B-blast furnace slag cement (“BFSC”) and fly ash as admixture. Replacement ratio of fly ash in FAC was 20% for all W/B. Crushed stone with nominal maximum size of 20 mm was used as coarse aggregate and sea sand as fine aggregate. Ratio of fine aggregate to total aggregate content (“S/(S+G)”) is varied to adjust the slump of all concrete types to designed slump of 8 ± 1 cm.

Table 1 Physical properties of materials used.
Table 2 Mix proportion of laboratory prepared concrete.

2.1.1 Casting and Curing

Cylindrical specimens were prepared with varied dimensions for each set of test (φ7.5 × 15 cm cylindrical specimens for compressive strength test, φ10 × 15 cm cylindrical specimens for air permeability and electrophoretic test, φ7.5 × 15 cm cylindrical specimens for accelerated neutralization test and φ10 × 10 cm cylindrical specimens for salt immersion test).

All concrete specimens were either water cured or atmosphere (Air curing) cured with relative humidity of 60% and 20 °C for 28 days.

2.1.2 Compressive Strength Test

Compressive strength test of cylindrical specimens of φ7.5 × 15 cm, water and atmosphere cured for 28 days were carried out in accordance with JIS A 1108. Average of three samples was taken for compressive strength (MPa: megapascal).

2.1.3 Air Permeability Test

Cylindrical specimens of φ10 × 15 cm were used prior to electrophoretic test. All specimens both water and atmosphere cured were further dried for a period of 7 days at relative humidity of 60% and 20 °C until no reduction in mass. The variation of air permeability result with different relative humidity was experimented and reported by Care and Derkx (2011) and Villani et al. (2014). However, in this study, this condition was adopted to match the conditions of laboratory during the air permeability experiment. The sides of specimens were coated with epoxy and taped with aluminum, except top and bottom surface to promote air flow into specimen. Compressed air was introduced into the chamber. When the amount of permeated air became constant, the amount of air permeation was measured by the water substitution method (Fig. 1). The air permeability coefficient or air permeability was calculated by Eq (1) (RILEM TC 116-PCD—permeability of concrete as criterion of its durability). Where, P1 = 1.6 kgf/cm2, P2 = 1.0332kgf/cm2, r = 1.025 × 10−6kg/cm3.

$$ K = \frac{{2hP_{2} r}}{{P_{1}^{2} P_{2}^{2} }} \times \frac{Q}{A} $$
(1)

where, K: air permeability coefficient (cm/s), P1: Load pressure (kgf/cm2), P2: Barometric pressure (kgf/cm2), h: Thickness of specimen (cm), Q: Volume of air permeated (cm3/s), A: Area of air permeated (cm2), r: mass per unit volume of air (kg/cm3), cm: centimeter = 10−2m, kgf: kilogram-force = 9.81 N, cm2 = 10−4m2, cm3 = 10−6m2.

Fig. 1
figure 1

Air permeability test setup.

2.1.4 Accelerated Neutralization Test

Cylindrical specimens of φ7.5 × 15 cm both water and atmosphere cured for 28 days were epoxy coated except test surface to promote pH neutralization (henceforth referred as “neutralization”) under CO2 concentration of 5%, temperature of 20 ± 2 °C and relative humidity of 60% as per JIS A 1153. At predetermined promotion periods of 30, 60, 90, 120, 150 days specimens were cut open to measure the neutralization depth by phenolphthalein spray method. Neutralization coefficient (mm/√year, mm: millimeter = 10−3m) was also calculated using simple equation based on Fick’s first law.

2.1.5 Salt Immersion Test

Salt immersion test and determination of diffusion coefficient were done according to JIS A 1154 and JSCE-G572 respectively for specimens both water and atmosphere cured. Cylindrical specimens of φ10 cm × 10 cm were used for salt immersion test. The side and bottom surface were coated with epoxy, except top surface for the test after which specimens were immersed in 10% concentration of NaCl solution for 91 days. Specimens were drilled from the test surface to collect powder for every 5 mm thickness interval up to 40 mm. Total chloride ion content was determined and diffusion coefficient, Da (cm2/year, cm2 = 10−4m2) was calculated up to a depth of 10 mm using Fick’s second law of diffusion.

2.1.6 Electrophoretic Test of Chloride Ion

Cylindrical specimens of φ10 cm × 5 cm were used after air permeability test. These specimens were coated with epoxy on the sides except opposite surfaces. And, chloride ion diffusion coefficient, De (cm2/year, cm2 = 10−4m2) was determined in accordance with JSCE-G571.

2.1.7 Porosity

Mercury intrusion porosimetry was employed to determine the pore size distribution of each concrete. Pore sizes are represented in nanometers (nm = 10−9m).

2.2 Concrete Cores Obtained from Concrete Structure Exposed to Marine Conditions

In this experiment, concrete cores of actual structure in marine environment were used as specimens. The 23-year-old concrete structures were constructed using B type Portland blast furnace cement and partial replacement of cement by fly ash. For concrete with type-B blast furnace cement (here-in-after referred as “BB”) W/B was 65% and compressive strengths of 31.3 and 28.9 MPa at splash zone and tidal zone area, respectively. On the other hand, in case of concrete with fly ash partially replacing cement (here-in-after referred as “FA”), W/B was 45, and 30% replacement with fly ash. Compressive strength was 39.6 MPa and 41.2 MPa in splash and tidal zone, respectively.

Cores of φ9 cm × 20 cm were extracted from exposed concrete structure at tidal and splash zones. Tests were carried out by using cut slices of the concrete core as shown in Fig. 2. Measurement of penetrated chloride ion was carried out in accordance with JIS A 1154. Slices of 1 cm were taken up to depth of 5 cm to obtain chloride content profile along the depth of concrete. The chloride diffusion coefficient then determined for top portion of concrete exposed to sea is represented as “Dc”. Area of concrete without chloride ion content (not directly exposed to sea, bottom 10 cm portion) was used for air permeability test, salt immersion test and electrophoretic test of chloride ion. Air permeability, salt immersion, electrophoretic test and porosity tests were carried out similar to the procedures explained in Sect. 2.1. Salt immersion test was done for a period of 200 days.

Fig. 2
figure 2

Exposed concrete core.

3 Results and Discussion

3.1 Laboratory Prepared Concrete

3.1.1 Relationship Between Air Permeability, Water Binder Ratio and Compressive Strength

The relationship between air permeability and water binder ratio of concretes are shown in Fig. 3. The difference in curing conditions is also projected in the graphs. Regardless of cement types used, air permeability is lesser for water cured specimens than atmosphere cured similar to other findings (Mu et al. 2015). Water cured OPC concrete is found to have lesser permeability at lower W/B compared to FAC and BBC and higher as the W/B increases. Atmosphere cured BBC and FAC show higher permeability. The difference in permeability between curing conditions of BBC and FAC for same W/B tend to increase compared to OPC. Figure 4 shows the relationship between the compressive strength and permeability coefficient after 28 days of concrete curing.

Fig. 3
figure 3

Air permeability versus water binder ratio.

Fig. 4
figure 4

Air permeability versus compressive strength.

Permeability coefficient in any cement types, decreases with increase in compression strength regardless of curing conditions. Relationship with the air permeability coefficient and the compressive strength showed high correlation with R2 = 0.9587 for OPC, R2 = 0.9289 for BBC and R2 = 0.9261 for FAC. However, FAC and BBC show lesser correlation than OPC suggesting the effect of curing conditions which showed large differences in permeability for different curing conditions for FAC and BBC. Hence blended concrete requires water curing for longer curing periods.

3.1.2 Relation Between Air Permeability, Neutralization Coefficient and Compressive Strength

Figure 5 shows the relationship between the neutralization coefficient and air permeability. Neutralization coefficient increases for any cement type with increase in W/B, and with increase in air permeability (Basheer et al. 2001; Khunthongkeaw et al. 2006; Neves et al. 2015), which means W/B, air permeability, neutralization coefficient and compressive strength are all highly correlated (Sanjuan and Munoz-Martialay 1996; Hui-sheng et al. 2009; Neves et al. 2015; Salvoldi et al. 2015). Between cement types, for same W/B, curing condition and air permeability, OPC shows less neutralization compared to BBC and FAC similar to the findings of (Bijen 1996; Khunthongkeaw et al. 2006). OPC has relatively higher content of cement and hence produces higher amounts of calcium hydroxide. This is thought to be the cause for reduced neutralization. Higher the compression strength lower is the neutralization coefficient for OPC, BBC, and FAC but showing varied correlation with different curing conditions (Fig. 6, shows relationship between compressive strength and neutralization coefficient).

Fig. 5
figure 5

Air permeability versus neutralization coefficient.

Fig. 6
figure 6

Compressive strength versus neutralization coefficient.

By comparing the relationship between air permeability coefficient and the neutralization coefficients shown in Fig. 5, neutralization coefficient is highly correlated with the compression strength for all types of cement which is in line with other studies (Al-Amoudi et al. 2009; Guiglia and Taliano 2010; Neves et al. 2015). But those studies showed rather less correlation between air permeability and neutralization suggesting that estimation would be better considering compressive strength. Since in the present study air permeability, compressive strength and neutralization all show high correlation, it is suggested that estimation of neutralization rate by air permeability coefficient can be done by taking into account the W/B, cement types and curing conditions. But BBC is not much affected by W/B as compared to others. A similar argument is made by Hui-sheng et al. (2009).

3.1.3 Chloride Penetration and Air Permeability

Corresponding to decrease in air permeability coefficient in any of the cement type, Da decreases (Fig. 7, shows relationship between air permeability and chloride diffusion coefficient by salt immersion test, “Da”). Fairly good correlation is found between diffusion coefficient and air permeability for all cement types. According to Sugiyama et al. (1996), correlation exists in the range where water cement ratio significantly effects air permeability. As in Fig. 7, water cured specimens show low diffusion coefficient than atmosphere cured. According to Ramezanianpour and Malhotra (1995) and Guneyisi et al. (2009), lack of moist curing significantly lowers concrete resistance to chloride penetration and even more in blended cements, similar to results found in the present study. Especially, BBC and FAC show very low diffusion coefficient (Bijen 1996; Leng et al. 2000), but in the present case even when atmosphere cured. Concrete with slag shows superior resistance to chloride penetration (Yildirim et al. 2011). Cement type, W/B and curing condition are very influential factors concerning chloride penetration (Song et al. 2008; Guneyisi et al. 2009; Yildirim et al. 2011). For low W/B, even though air permeability differs largely between curing conditions, Da show less difference. Atmosphere cured concretes show greater variation in air permeability and Da for all W/B than water cured concretes suggesting that the pore structure can alter the chloride transport in concrete. Hence from the observations, it can be understood that chloride penetration is much strongly governed by chemical processes (ion transfer and physical adsorption by charge interaction, concentration gradient, and immobilization) rather than physical processes (advection) alone. From the observations, when estimating the chloride ion apparent diffusion coefficient by permeability coefficient, it is necessary to take into account at least the cement type and curing conditions.

Fig. 7
figure 7

Air permeability versus apparent chloride diffusion coefficient by salt immersion test.

Figure 8 shows the relationship between the effective chloride diffusion coefficient, De, determined by electrophoretic test and permeability coefficient. Within the scope of the results shown in Fig. 8, regardless of cement type, those subjected to water curing, show fairly high correlation between the permeability coefficient and De, but for atmosphere cured concrete, the correlation with cement type is less. In the case of atmosphere cured concrete subjected to vacuum during air permeability test and later saturated when subjected to electrophoretic test changes the internal conditions of concrete; from dry concrete including unreacted cement to saturated concrete with possible rehydration reaction. This results in varied air permeability results before and after the tests. Hence, this is thought to be one of the reasons for low correlation for atmosphere cured concrete. The degree of saturation highly effects chloride diffusion (Nielsen and Geiker 2003). Overall result shows lower permeability for water cured specimens than atmosphere cured (Care and Derkx 2011). The possibility of estimating De without considering cement types by permeability coefficient can be considered but moisture condition and curing are accountable. However, further investigation is recommended to clearly understand the correlation and possible estimation by air permeability.

Fig. 8
figure 8

Air permeability versus effective chloride diffusion coefficient by electrophoretic test.

3.2 Exposed Concrete to Actual Marine Conditions

Figure 9 shows the relationship between the air permeability coefficient, chloride diffusion coefficient (Dc) of exposed concrete core (up to 5 cm from surface depicted in Fig. 2), and chloride diffusion coefficient (Da) by salt immersion test for 200 days of bottom part not affected by chloride. In the figure, “BB splash” means upper part of concrete core up to 5 cm which was exposed to marine condition and “BB splash 200” means bottom part of concrete core subjected to salt immersion test for 200 days. Correlation between air permeability and Dc is not confirmed in the case of exposed part but higher degree of correlation for Da by salt immersion test for 200 days. The difference in apparent diffusion coefficient between sea condition and immersion test is due to time dependent declination of diffusion coefficient due to the long-term hydration reaction of cement or blended cements (Takewaka and Matsumoto 1988; Costa and Appleton 1999). However, there are several other factors to be considered for marine exposed concrete. This makes it more complicated to arrive at relationship between permeability and chloride penetration. Figure 10 shows the relationship between the air permeability and De. De seems to be higher for higher air permeability in any concrete. Although the measured points are few, it is suggested that air permeability coefficient and De have significant correlation, unlike Da or Dc. Sharif et al. (1997) and Tegguer et al. (2013) also showed a highly correlated linear relationship between chloride diffusion and air permeability (Sharif et al. 1997; Tegguer et al. 2013). These findings show that air permeability can be an alternative to chloride diffusion obtained by electrophoretic test.

Fig. 9
figure 9

Air permeability versus chloride diffusion coefficient by salt immersion test (Da) and chloride diffusion coefficient of marine exposed concrete (Dc) for exposed concrete.

Fig. 10
figure 10

Air permeability versus effective chloride diffusion coefficient (De) for exposed concrete.

Specimens which were water cured showed high correlation regardless of cement types and water cement ratio in Fig. 8. And, this relationship differs from Fig. 10 due to the influence of water content ratio in concrete. Incidentally, water content ratio was 60% in exposed concrete core at sea condition, and 75% in prepared concrete when measuring air permeability. It is a well-known fact that air permeability is influenced by water content in concrete and that pre-conditioning is required which makes the test often sensitive (Zaharieva et al. 2003). The difference in slope of correlation between Figs. 8 and 10 is assumed to be the effect of difference in water content rate when measured. In case of laboratory prepared atmosphere cured concrete, low correlation was observed between air permeability and De due to the changes in pore structure of concrete when concrete is transferred from air permeability test to electrophoretic test because of possible rehydration reaction of cement in the process of electrophoretic test of chloride ion and saturated water processing.

The results of air permeability depend on degree of saturation of specimen under test and how it is dried (Sugiyama et al. 1996). Hence, estimation of De by air permeability for laboratory prepared concrete and actual structure exposed to marine conditions is possible by considering the effect of water content ratio. From these results, De can be estimated by measurement of air permeability regardless of cement type or concrete properties, but water content should be considered.

Effects of pore structure on diffusion coefficient of BBC and FAC in existing structure is evaluated as a relationship between volume of pores for a range of pore diameter and respective diffusion coefficients by linear approximation method depicting correlation coefficient R2.

The diffusion coefficient of all concretes combined versus pore volume of respective concrete for a particular range of pore size (say 200–500 nm marked as vertical block in Fig. 11a) is plotted and R2 is determined as illustrated by Fig. 11. Similar procedure is followed for air permeability, Da, De versus pore volume for other pore size range (for ex; 50–100 nm, 500–1000 nm) and R2 values are determined. The R2 values obtained for varied pore size ranges are then plotted as shown in Fig. 12. The Dc of top portion of concrete core exposed to marine condition had the highest correlation coefficient for pore diameter range of 50–200 nm, and decreased with increasing pore size in concrete. On the other hand, Da of concrete core bottom portion subjected to immersion test had greatest correlation coefficient between pore diameters from 200 to 1000 nm, confirming large effect of pore diameter in comparison with marine exposure. It is found that effect of pore diameter on penetration of chloride ion under various conditions is different. This is attributed to the fact that, penetration property of chloride ion under the marine condition is greatly affected by the capillary pores of diameter 200 nm or below due to repeated wet and dry cycles in splash zone and tidal zone. Whereas salt immersion and electrophoretic test specimens are under saturated condition and chloride diffusion becomes predominant. Large pores influence chloride diffusion. Air permeability also is affected by large pores. This is evident from Fig. 12 where correlation coefficients of air permeability and De tend to increase with increase in pore diameter. Especially, significant correlation is found in pore diameters larger than 1000 nm. Influence of pore diameter on air permeability and De is found to be similar. Therefore they are considered as highly correlated.

Fig. 11
figure 11

An example showing the determination of R2 between Dc and pore volume, a pore distribution of concretes exposed to marine conditions and b Dc versus pore volume for all concretes between pore size of 200–500 nm.

Fig. 12
figure 12

Correlation coefficient of durability indicators for exposed concrete at different pore sizes.

Figure 13 shows the correlation coefficients in comparison with pore diameter range for laboratory prepared concretes. The Da is highly correlated for pore diameter between 200 nm and 1000 nm, and correlation coefficient (R2) decreased with increasing pore diameter. On the other hand, correlation coefficient (R2) for De and air permeability tends to increase with increase in pore diameter in concrete similar to the trend shown in Fig. 12. Especially, effect of pore diameter larger than 1000 nm is significant.

Fig. 13
figure 13

Correlation coefficient of durability indicators for laboratory prepared concrete at different pore sizes.

The trends observed for De and air permeability are similar in both cases of laboratory prepared concrete and concrete exposed to actual marine conditions and therefore they are observed to be highly correlated. The air permeability and effective chloride diffusion coefficient (“De”) by electrophoretic test depend on pore structure. The pore structure of concrete is in turn affected by cement types and curing conditions. Long term exposure to marine conditions can change the pore structure of concrete. However, it is found that the air permeability and effective chloride diffusion by electrophoretic test are correlated. Hence, from the present study, chloride diffusion coefficient can be estimated from the results of air permeability for laboratory prepared concrete and concrete exposed to marine condition, with due consideration to moisture content of concrete.

4 Conclusions

An attempt has been made in understanding the relationship between air permeability and durability indicators like neutralization and chloride penetration. Experimental investigations are done to elucidate the application of air permeability as an alternative to chloride penetration tests and neutralization tests for both laboratory prepared concrete and for concrete exposed to marine conditions. From the results obtained following conclusions are drawn:

  1. 1.

    Air permeability is highly correlated with water cement ratio, compressive strength and neutralization. Air permeability can be used as an alternative to neutralization coefficient with due consideration to water cement ratio, curing condition and cement type.

  2. 2.

    Air permeability is found to be fairly correlated with chloride diffusion coefficient and the degree of correlation depends on type of tests and curing conditions. When using air permeability as an alternate to chloride diffusion coefficient, cement types and curing conditions plays a significant role.

  3. 3.

    Chloride diffusion by electrophoretic test is better correlated with air permeability than salt immersion test. The estimation of effective diffusion coefficient by air permeability is possible regardless of cement types, but moisture content and curing condition must be taken into account.

  4. 4.

    The apparent chloride ion diffusion coefficient obtained by immersion test of marine exposed concrete samples is affected by pore diameter between 200 and 1000 nm. In the case of wet-dry cyclic condition, smaller pore diameter affects the apparent chloride ion diffusion coefficient for marine exposed concrete. Less correlation is seen between air permeability and diffusion coefficient which is attributed to time-dependent declination of diffusion coefficient due to continued hydration in concrete over longer period.

  5. 5.

    The pore diameter has significant effect on air permeability and chloride ion diffusion coefficient by electrophoretic test, which differ from apparent diffusion chloride ion coefficient, and both are very likely to be affected by the relatively large pore diameter.

  6. 6.

    The air permeability and effective chloride diffusion by electrophoretic test are correlated for laboratory prepared concrete and concrete exposed to marine condition. Hence present study affirms that the chloride diffusion coefficient can be estimated from the results of air permeability with due consideration to moisture content of concrete. This finding provides an experimental tool for assessment of durability.