Abstract
Product testing is widely used to assess the characteristics, e.g. performance and energy consumption of a product. The procedures for executing the tests, including measurements and processing of measurement results, can be contained in standards. Standards should produce results that are repeatable, reproducible and valid at a reasonable cost. A number of stakeholders have questioned the appropriateness of several standards because the results that these standards provide are different from what a consumer may experience in practice. In the end, this can have negative consequences for the trust of consumers in the policy instruments (energy labels, minimum efficiency requirements) that use these standards and an energy savings deficit compared to what was expected by policy-makers. There is, therefore, a need for standards that better reflect ‘real-life’ conditions, meaning those conditions that consumers experience at home. However, unlike the other criteria that standards should meet, there is no methodology to assess the representativeness of a standard. This article develops such a methodology and presents the results for several household electrical appliances: washing machines, refrigerators and vacuum cleaners. In general, variation of situational conditions is not reflected in the standards and important parts of use behaviour are implemented as ‘artificial’ in the standards, showing that the other criteria (repeatability, reproducibility and cost) are prioritised over representativeness. Assessment of performance is difficult to evaluate because the type of assessment differs between practice and test; additional research is needed in this area.
Similar content being viewed by others
Notes
Terminology Note: The term ‘correspondence’ refers to the comparison of values or behaviour as observed in practice (at consumers’ homes) versus what is defined upon in the relevant standard (In other words: What is the difference between values and behaviour in the standard and real life?). On the contrary, ‘representativeness’ is a term which is used here to express an assessment on a parameter or standard based on correspondence (In other words: Is this difference acceptable?). Finally, ‘consumer-relevance’ is, in turn, an overarching term to express the result of the assessment on a standard, based primarily on representativeness but also considering the other three criteria listed (In other words: What is the balance?). In that sense, correspondence is observed, whereas representativeness and ‘consumer-relevance’ are assessed.
References
AEA (2009). AEA energy & environment. Work on preparatory studies for eco-design eequirements of EuPs (II) Lot 17 vacuum cleaners. https://www.eup-network.de/fileadmin/user_upload/Produktgruppen/Arbeitsplan/eup_lot17_final_report_issue_1.pdf. Accessed 2 Aug 2018.
Bundesanstalt für Materialforschung und –Prüfung, (2016). http://www.bam.de/de/aktuell/presse/pressemitteilungen/pm_2016/pm02_2016.htm. Accessed 18 Oct 2017.
ComplianTV. (2015). Compliance of TVs with energy label and ecodesign requirements. Final Publishable Report. http://www.compliantv.eu/eu/about-the-project/all-documents. Accessed 18 Oct 2017.
EC (2015). European Commission. M/540 Commission Implementing Decision of 11.12.2015 on a standardisation request to the European standardisation organisations in support of Commission Delegated Regulation (EU) No 665/2013 of 3 May 2013 supplementing Directive 2010/30/EU of the European Parliament and of the Council with regard to energy labelling of vacuum cleaners and Commission Regulation (EU) No 666/2013 of 8 July 2013 implementing Directive 2009/125/EC of the European Parliament and of the Council with regard to ecodesign requirements for vacuum cleaners. ftp://ftp.cencenelec.eu/CENELEC/EuropeanMandates/M540_EN.pdf. Accessed 18 Oct 2017.
EU (2017). Regulation (EU) 2017/1369 of the European Parliament and of the Council of 4 July 2017 setting a framework for energy labelling and repealing Directive 2010/30/EU. https://eur-lex.europa.eu/eli/reg/2017/1369/oj. Accessed 2 Aug 2018.
IEA (2009). Gadgets and gigawatts: Policies for energy efficient electronics. Paris: OECD Publishing. https://doi.org/10.1787/9789264059542-en. Accessed 2 Aug 2018.
IEC (2017). International electrotechnical commission. Vision and mission. http://www.iec.ch/about/values/service.htm. Accessed 7 Oct 2017.
ISO 5725-2 (2002). Accuracy (trueness and precision) of measurement methods and results—part 2: Basic method for the determination of repeatability and reproducibility of a standard measurement method (ISO 5725-2:1994 including technical corrigendum 1:2002), Geneva. https://www.iso.org/standard/36202.html. Accessed 2 Aug 2018.
ISO/IEC 17025. (2005). General requirements for the competence of testing and calibration laboratories, 2nd edn, Geneva. https://www.iso.org/standard/39883.html. Accessed 2 Aug 2018.
ISO/IEC 17043. (2010). Conformity assessment—general requirements for proficiency testing. Geneva. https://www.iso.org/standard/29366.html. Accessed 2 Aug 2018.
JRC (2016). Ecodesign and energy label revision: household washing machines and washer-dryers. http://susproc.jrc.ec.europa.eu/Washing_machines_and_washer_dryers. Accessed 18 Oct 2017.
Kruschwitz, A., Karle, A., Schmitz, & Stamminger, R. (2014). Consumer laundry practices in Germany. International Journal of Consumer Studies, 38(3), 265–277.
Meier, A. K., & Hill, J. E. (1997). Energy test procedures for appliances. Energy and Buildings, 26(1), 23–33.
Pearce, E., Procter & Gamble. (2005). Proceedings of the 42nd International detergency conference 31 May – 2 June 2005, WfK, Krefeld.
Siderius, P.J.S. (1991). Testing washing machines; test methods for measuring performance. SWOKA research report 112, The Hague.
Sivitos S., Spiliotopoulos C., Stamminger R., Toulouse E. (2015). Don’t just press the button!—why appliance settings increasingly matter for efficiency delivery and rulemaking. http://ecostandard.org/wp-content/uploads/Appliance-Settings-and-product-efficiency.pdf. Accessed 18 Oct 2017.
Spiliotopoulos, C. (2016). How product testing practices contribute to the loss of energy savings, and how to prevent it. http://ecostandard.org/wp-content/uploads/ECOS-Testing-Methods-Paper-Final.pdf. Accessed 18 Oct 2017.
Terpstra, P. M. J. (2000). Assessment of cleaning efficiency of domestic washing machines with artificial soiled test cloth. Bonn: Institut für Landtechnik, Rheinische Friedrich-Wilhelms-Universität.
Toulouse, E. (2014). Developing measurement methods for EU Ecodesign and energy labelling measures. A discussion paper. CLASP, Brussels. http://clasp.ngo/~/media/Files/SLDocuments/2014/2014_02_Measurement-Methods-ED-and-EL-Measures.pdf. Accessed 18 Oct 2017.
VHK and Armines. (2016). Preparatory study revision cold appliances regulations. http://www.ecodesign-fridges.eu/Pages/introduction.aspx. Accessed 18 Oct 2017.
Yates, L., & Evans, D. (2016). Dirtying linen: re-evaluating the sustainability of domestic laundry. Environmental Policy and Governance, 26(2), 101–115.
Acknowledgements
The authors thank CLC/TC 59X, especially Dr. Gerhard Fuchs, Mr. Alain Roux, Mr. Paul van Wolferen, Mr. Bernhard Scheuren and Mr. Jeremy Tait for their contribution and data provision and two anonymous reviewers for their comments.
Author information
Authors and Affiliations
Corresponding author
Ethics declarations
Conflict of interest
The authors declare that they have no conflict of interest.
Annex
Annex
Assessment of consumer-relevance of three example standards
Example 1: washing machines
Steps 1a, 2a and 3: Listing parameters, selecting (most) relevant parameters, assessment of correspondence
Parameters | Relevance for energy consumption (E) or performance (P)a | Range; average at consumerb (sources: preparatory study, (JRC 2016) EN 60160) | Setting/variation in standard (Source: EN 60456, IEC 60734) | Assessment of correspondence | Explanation of differences between standard and practice | |
---|---|---|---|---|---|---|
Situational conditions | ||||||
Temperature | Medium | E | > 0 to 40 °C; average | 23 ± 2 °C | Average corresponds; variation not | Variation in standard is smaller than practice to respect working conditions and air conditioning costs in the lab |
Humidity | Low | 0 to ~ 100% r.h.; average | Not specified | No assessment possible | ||
Inputs | ||||||
Voltage | Medium | E, P | 207–253 V; 230 V | 230 V ± 1% | Average corresponds; variation not | Rated voltage in Europe |
Frequency | Low | 49–51 Hz; 50 Hz | 50 Hz ± 1% | Average and variation correspond | Rated frequency in Europe | |
Harmonic distortion | Low | E | Distorted | Plane sinus | No correspondence | |
Water hardness | High | P | 0 to > 10 mmol/l; average | 2,5 mmol/l | Average corresponds; variation not | Performance assessment at different water hardness is subject of detergent manufacturer. |
Water composition (e.g. metal content) | Medium | P | Potable water | Not specified. Water has to fulfil the water hardness specification. If total water hardness needs to be adjusted, it shall be prepared according to IEC 60734. | No assessment possible | Performance assessment at different water composition is subject of detergent manufacturer. |
Water temperature | High | E, P | 4 to ~ 25 °C; 15 °C | 15 ± 2 °C | Average corresponds; variation not | Global average |
User behaviour | ||||||
Washing programme choice (Depends on type, soiling and load) | High | E, P | Cotton (60% choice), mixed, synthetic, wool + temperature | Standard allows a wide range of programmes. | Standard corresponds with practice, by offering capture of various programmes. | Regulatory provisions specify the programmes to be tested. |
Type of cloths | High | E,P | Cotton, cotton—synthetic blends (20:80; 35:65; 50:50; etc.), wide range of synthetic fibres (PE, PAS, PP); wool, cellulose, viscose | (Standard-) cotton; standard also allows for other fabrics than cotton to be tested | Standard corresponds with practice, by offering capture of various fabrics. | Regulatory provisions specify the fabrics to be tested. |
Soiling of cloths - quality - quantity | High | P | Natural soiling from food, body soils, ambient soil. Type of soils: soluble and insoluble soils, particular soil, colour soil A typical 3-kg Western European laundry load contains an average of 40 g of soil. (Pearce et al. 2005) | Artificial soiling of: carbon/oil, cacao, sebum, red wine, and blood, with as little variation as possible. One soil strip used per kg of loading capacity. One strip contains about 2.5 g of dried-on soils. Note that standard soil is more challenging to remove than natural soiling. | Correspondence on type of soil, not on quantity | High soil level needed to prove the machine is able to extract soil even at those conditions. Adherent soil needed to allow detecting measurable differences. Artificial soiling in standard for reproducibility and cost reasons |
Load | High | E, P | < 1 kg to maximum of drum capacity (11 kg); average 3 kg | Standard allows testing from 1 to 15 kg | Standard corresponds with practice. | Regulatory provisions specify the loads to be tested: maximum (rated) capacity and its 50%. |
Detergent type and amount | High | P | Powder, liquid, gel, or tablet; heavy duty/light duty; various compositions depending on brand/time. Amount according to detergent manufacturer or fixed amount or relative to load/soiling. Consumer research in Germany shows average amount of detergent dose of about 70 g (Kruschwitz et al. 2014) for an average load of 3.3 kg | Heavy duty powder detergent of fixed composition and dosed following formula depending on load size. Formula to calculate: 0 + 12 g/kg load. Fixed amount (40 g) needed for an empty drum. 12 g is added per kg of textile load (and soil strip) to achieve about an equal concentration for all load sizes, as more water is taken by the machine the more load is washed. | Average amount corresponds with practice. Differences in composition not. Differences in type (liquid) not. | Artificial detergent in standard for reproducibility reasons. Market detergents are changing continuously with time. |
Product features | ||||||
Capacity | High | E, P | 3 to 11 kg; average 6.5 kg. | Manufacturer must show that the machine allows to clean clothes at highest level of filling which can be assumed to happen (with those clothes used for testing) | Standard corresponds with practice. | Maximum capacity captured by regulatory provisions. |
Steps 1b and 2b: Listing of all performance aspects, selecting (most) relevant aspects, assessment of correspondence
Aspects of performance | Remarks | Assessment in practice | Assessment in standard |
---|---|---|---|
Removal of stains | Wide range of stains. Not all stains get always removed | Visual inspection of stains | Measured with reflectometer |
Greying | Multi cycle effect | Visual inspection | Not assessed |
Incrustation | Depending on washing conditions | Hardening of the textile | Not assessed |
Textile strength loss | Multi cycle effect | Damage of textiles | Not assessed |
Gentleness of action? | Multi cycle effect | Damage of textiles | Not assessed |
Pilling effect | Multi cycle effect | Visual inspection | Not assessed |
Colour damage | Depending on dye | Visual inspection | Not assessed |
Dye transfer | Depending on dye | Visual inspection | Not assessed |
Rinsing of soluble parts | Depending on detergent used | feeling | Alkalinity (EN 60456) |
Rinsing of insoluble parts | Particles remaining | Not assessed | |
Rinsing of surface active ingredients | Feeling soapy | LAS rinsing (t.b.d.) | |
Rinsing performance—foam bubbles at end of cycle | Visual inspection | Not assessed | |
Wool shrinkage | Visual inspection | Measurable acc. to EN 60456 | |
Germ reduction | infection | Not assessed | |
Spinning efficiency | Tactile inspection | Remaining moisture content (RMC) at max spin speed | |
Water consumption | Not assessed | measured | |
Energy consumption | Not assessed | measured | |
Duration of programme | Experienced | measured | |
Noise of washing | Experienced | measured | |
Noise of spinning | Experienced | measured | |
Annoyance of noise? | Experienced | Not measured |
Step 3: Correspondence of assessment of performance
A number of aspects of performance are not assessed in the standard. For the aspects that are assessed in the standard, this is done through measurement instruments and not by human senses (seeing, feeling, smelling, hearing) as it is in practice.
Example 2 Household refrigerators
Steps 1a, 2a and 3: Listing parameters, selecting (most) relevant parameters, assessment of correspondence
Parameters | Relevance for energy consumption (E) or performance (P)a | Range; average at consumerb (source: VHK (2016)) | Setting/variation in standard (source: EN 62552: 2013, impact of IEC62552:2015) | Assessment of correspondence | Explanation of differences between standard and practice | |
---|---|---|---|---|---|---|
Situational conditions | ||||||
Temperature | High | E, P | > 0 °C to 40 °C; 20 °C | 16 and 32 °C. | Average to be determined; decision yet to be taken by the commission on which ambient temperature to adopt as that for the EU test | Via interpolation any value between 16 and 32 °C can be assessed. Likely that higher than usually encountered will be used for test to compensate for no door openings, no heat loading (food). |
Humidity | Low (if no door openings) | E, P | < 75% r.h. | Humidity is of limited relevance in test if doors closed. But it is of higher significance in real use where doors are opened regularly. Hence, typical EU ambient humidity should be considered. | ||
Air flow | Low (if no door openings) | E | No evidence identified on what is a typical air speed in EU kitchens | Air flow ≤ 0.25 m/s | Zero/low speed air is expected in a home most of the time. Also, the condenser is close against a partition and so the air flow is of little direct impact on condenser effectiveness. Air flow would have far more impact if door is opened. | |
Placing of the appliance during use/test | Medium | Refrigerators often pressed close against wall and between cabinets. Some are ‘built-in’ type. No evidence identified on what is the most common arrangement in EU homes | Placing against partition at rear unless specified (max. 50 mm from partition and 300 mm from sides, no partition above). Built-in appliances enclosed per manufacturer instructions. | Correspondence is reasonable for rear position, although most fridges in real use are pressed in from side without 300 mm gap to any partition. | Close-fitting side panels would impact thermal performance of appliance walls and reduce reproducibility. This could explain 300 mm gap introduced. | |
Inputs | ||||||
Voltage | Low | E | 207–253 V | 230 V ± 1% | Average corresponds; variation not | Rated voltage in Europe |
Frequency | Low | E | 49–51 Hz | 50 Hz ± 1% | Average and variation correspond | Rated frequency in Europe |
Harmonic distortion | Low | E | Distorted | Plane sinus | No correspondence | |
User behaviour | ||||||
Load: - Type (heat capacity) - Temperature - Amount | High | E, P | Various liquid and solid foods, input at various temperatures (5 to 40 °C) | No inserted heat load for EU regulation tests. | Appliance always has food or other loads in reality, but test for EU regulations is with appliance empty. Correspondence is poor, but compensation made via higher ambient test temperature | (Warm) load insertion under normal usage for energy label purposes (the energy efficiency test) is emulated by using higher ambient temperature than EU typical) |
Door openings | Low | E | 20 per day. | Currently not, but possible future simulation option via ‘load processing efficiency test’: loading with bottles of ambient temperature water (in one opening operation) | Door openings are emulated by higher ambient temperature (around 25 0C) and effect of door openings is small. | |
Defrost interval as a result of user behaviour and ambient conditions | Medium | E, P | No evidence sources identified so far. | Lack of door openings may not allow for consideration of frost thickness, defrost intervals and realistic energy consumption of defrost function. | ||
Thermostat setting | High | E, P | Target average air temperature of compartments specified; thermostat settings such that target temperatures achieved | |||
Arrangement of drawers/shelves | Medium | E, P | Instructions to maximise volume of colder space | Average corresponds; variation not | Arrangement in standard to measure at max conditions. | |
Product features | ||||||
Internal volume (capacity) | High | E, P | Difference between volume as measured by standard and volume experienced as ‘available’ to user for storing food: presence or not of shelves etc. for the measurement is a key element. | ‘Storage volume’ (‘usable’) current basis of calculation of equivalent volume used for EU regulation tests. However, IEC 62552: 2015 may no longer include ‘storage volume’, but ‘total internal volume’ (closer to ‘gross volume’) | Usable capacities substantially less than tested. Possible new ‘total internal volume’ substantially larger than ‘storage volume’ and over-statement would be even more exacerbated. | New IEC approach of total internal volume aims to simplify and improve repeatability, but in the expense of correspondence |
Climatic class | Medium | E, P | Difference between the average/typical EU climatic conditions, and the functionality (allowed to be) declared by the supplier for each test | SN, N, ST, T | Nearly 3/4 of fridges claim tropical performance capability (> 38 °C), temperature rarely existing in EU. Hence, there is poor correspondence with EU situation. | Compensation factor for T and ST class in regulation makes attractive to claim tropical (and sub-tropical) allowance. Fridges suitable for tropical usage get allowance of 20% higher equivalent volume in regulation; sub-tropical of 10% |
Built-in | High | E | Set-up per manufacturer’s instructions? | Specification per manufacturer’s instructions | OK | |
Frost free (defrost) | High | E | Market data: 40% has frost free function | Standard allows for measuring energy consumption of defrost. | ||
Ice maker | Low (depend on ice production) | E | Measuring energy consumption of ice-maker when ‘ready for use’, but no ice production | |||
Anti-condensation heaters | IEC 2015: If always on in normal use, then on for test; if user-controlled, test at max and min. | |||||
Other features, e.g. touchscreen/ internet | To be determined |
Steps 1b and 2b: Listing of all performance aspects, selecting (most) relevant aspects, assessment of correspondence
Aspects of performance | Remarks | Assessment in practice | Assessment in standard |
---|---|---|---|
Cooling performance | Ability to cool food within an hour or two and keep it cool despite door openings | Cooling capacity test covers this well. Variation in temperature measured | |
Freezing performance | Ability to freeze several items of food at once and keep all frozen over time | Freezing capacity test covers this well. Variation in temperature measured | |
Freshness of food | Visual assessment | None at present. | |
Size of storage space | Metric for measured storage volume, as available over shelves for foodstuff storage no longer in IEC and EN test | As experienced by the when filling the space | Was measured as ‘storage volume’ but no longer in IEC. The new metric of total internal volume is much larger and less useful to user. |
Food storage duration | Sensory assessment | Not assessed | |
Energy consumption | Not assessed (although indicated by proportion of time for which compressor is heard running) | Measured (with separate for defrost, ice-maker and anti-condensation but these do not appear on label) | |
Noise | Experienced | Measured |
Step 3: Correspondence of assessment of performance
Several important aspects of parameters, especially regarding user behaviour such as (warm) load insertion and door openings, are emulated in the standard by means of a higher ambient temperature. Repeatability and reproducibility have been given priority over mimicking user behaviour in practice. Calculations show that the chosen interpolated ambient temperature represent the worst-case situation; this assumption needs to be checked at further revisions. The main gaps in assessing the performance relate to functional aspects, e.g. freshness of food and food storage duration, for which neither a metric nor a test method is available yet. The energy service aspects of performance, providing cooling and freezing capacity, are well captured.
Example 3: vacuum cleaners
Steps 1a, 2a and 3: Listing parameters, selecting (most) relevant parameters, assessment of correspondence
Parameters | Relevance for energy consumption (E) or performance (P)a | Range; average at consumerb (source: AEA (2009)) | Setting/variation in standard (source: EN60312) | Assessment of correspondence | Explanation of differences between standard and practice | |
---|---|---|---|---|---|---|
Situational conditions | ||||||
Temperature | Low | E | > 0 °C to 40 °C; 21 °C | 23 ± 2 °C | Average corresponds; variation not | Stricter variation in test due to lab climate conditions |
Humidity | Low | P | 50 ± 5% rH | No assessment possible | ||
Inputs | ||||||
Voltage | Low | E, P | 207–253 V; 230 V | 230 V ± 1% | Average corresponds; variation not | Rated voltage in Europe |
Frequency | Low | 49–51 Hz; 50 Hz | 50 Hz ± 1% | Average and variation correspond | Rated frequency in Europe | |
Harmonic distortion | Low | E | Distorted | Plane sinus | No correspondence | |
User behaviour | ||||||
Choice of nozzle - type - number | Medium High | E, P | Floor cleaning: consumers usually use one multipurpose (combination) nozzle. Less usage of special nozzles for special purposes. Above the floor cleaning: several nozzles used like upholstery nozzle, dusting brush, crevice tool | Partly covered in the standard: Floor cleaning: carpets, flat hard floors, hard floors with crevices Above the floor cleaning: fibre pick-up from upholstery | Floor cleaning: corresponds Above the floor cleaning: corresponds partly | Above the floor cleaning: far too many different kinds of potential usage |
Cleaning head setting | Medium High | E P | Not included but under development (currently in EU guidance documents) | No assessment possible | Few data regarding customers’ behaviour regarding usage of various attachments and settings available | |
Motor settings | High | E, P | Full power | Maximum continuous airflow | Standard corresponded to practice in the past. Currently, more complexity due to extended instructions in the manual. More vacuum cleaners with automatic power settings on the market | Increasing complexity of vacuum cleaners makes it more and more difficult to find a proper definition in the standard to cover all potential settings and simultaneously not being in contradiction with the existing regulations (EC 2015) |
Surface to be cleaned | High | P | Hard floor, carpet, upholstery | Flat hard floor, hard floor with crevices, carpet. 4 carpets specified, including the Wilton wool test carpet | Variation in carpets in principle captured but not implemented (single carpet used) | Use of single carpet due to cost and repeatability |
Dust particle size | High | P | Between 0.09 and 0.2 mm | Low correspondence because no debris included | Discussion started to evaluate options with different types of dust like debris | |
Product features | ||||||
Maximum usable volume of the dust receptacle | Medium | P | Not assessed |
Steps 1b and 2b: Listing of all performance aspects, selecting (most) relevant aspects, assessment of correspondence
Aspects of performance | Remarks | Assessment in practice | Assessment in standard |
---|---|---|---|
Dust pick-up | Measured with empty dust receptacle. Half-loaded receptacle test under preparation | Visual inspection. | Amount of dust in receptacle when test on carpet. On hard floor, dust amount left on floor is measured. Both after 5 double strokes |
Motion resistance | Experienced force during operation | Force to move cleaning head measured | |
Fibre and thread removal | Visual inspection | Measured | |
Performance with loaded dust receptacle | Visual inspection | Measured | |
Filter water loss | Experienced. | Measured | |
Filtration efficiency | Amount of dust in the intake aerosol channel | ||
Dust re-emission/filtration efficiency | A good evaluation of vacuum cleaner, not only filters used. | Highly relevant for allergy sufferers | Measured |
Total emission while vacuum cleaning | Evaluation of total system (including attachments) used on a soiled floor | Highly relevant for allergy sufferers | Measured |
Energy consumption | |||
Energy consumption | Not assessed | Measured | |
Operational aspects | |||
Ease of use / usability aspects | Experienced | Measured. Several tests: cleaning under furniture, radius of operation, flexibility of the hose, mass/dimensions, weight in hand | |
Noise | Experienced | Measured | |
Sustained performance | Experienced | Measured | |
Durability aspects | Experienced | Several durability tests on appliance and components (motor, hose, tube, cable reel, nozzles) |
Step 3: Correspondence of assessment of performance
The main aspects of performance are assessed in the standard. However, the way in which these aspects are assessed does not include any feedback during the operation. Contrary in practice, a consumer gets visual feedback about dust pick-up, feels the force needed to move the head and will react on this. The dust re-emission is almost impossible to relate to consumer experience, because the particle sizes are chosen to reflect particles harmful for the health of the consumer. This is different for allergy sufferers—they experience directly dust emitted or raised by the vacuum cleaner.
Rights and permissions
About this article
Cite this article
Spiliotopoulos, C., Stamminger, R. & Siderius, HP. Bringing the home in the lab: consumer-relevant testing for household electrical products. Energy Efficiency 12, 281–298 (2019). https://doi.org/10.1007/s12053-018-9718-5
Received:
Accepted:
Published:
Issue Date:
DOI: https://doi.org/10.1007/s12053-018-9718-5