Introduction

Iron and steel pipes have been used in water distribution systems for over five centuries [1]. Galvanized (zinc-coated) steel was the dominant pipe material for most of the twentieth century and is still installed in buildings today. Economically, modern zinc-coated steel pipes are inexpensive and recyclable. With a long life span, such material is very attractive. Zinc coatings protect steel by providing a physical barrier as well as cathodic protection for the underlying steel. In this process, zinc, as a more ignoble metal, acts as a sacrificial anode, while steel (as a cathode) is not attacked. However, there are many reports of galvanized steel water pipe failures due to corrosion after several months or few years of service life [2, 3]. Accelerated corrosion occurs under certain conditions of flow water chemistry. The internal wall of the steel pipe, exposed to aqueous environment (flowing water), usually suffers more severe corrosion (so-called internal corrosion) than the external wall exposed to indoor conditions [4]. Many water distribution systems begin to experience pinhole leaks caused by pitting corrosion on the internal surfaces of the piping. Zinc corrosion in flowing water is a complex process controlled largely by water chemistry and temperature. Relatively small differences in water chemistry can produce relatively substantial changes in corrosion products and rate. A coating of zinc protects galvanized pipe, but when corrosion occurs, it deposits high levels of zinc and iron into the tap water. A zinc coating on galvanized pipe may contain lead, copper, cadmium, chromium, aluminum, barium and other impurities. As a result of these impurities, corrosion of galvanized pipe may result in the release of trace metal concentrations [5,6,7,8,9,10,11]. Galvanized pipes are suitable only when the pH of the natural water is about 7 or moderately basic (between 8 and 12) [7].

According to the European Standards [12, 13], there are conditions under which galvanized steel pipes will sustain corrosion damage. One of the main factors influencing corrosion of zinc-coated pipes is water composition. The influence of chloride, nitrate and sulfate ions on pitting corrosion is determined by the so-called concentration ratio S1, the sum of chloride, nitrate and sulfate ion concentrations divided by the hydrogen carbonate ion concentration. According to these standards, pitting corrosion of zinc-coated steel pipes is extremely unlikely with S1 below 0.5 and very likely with S1 above 3.

Contemporary regulations in many countries even prohibit the use of galvanized steel pipes in drinking water systems and do not recommend them for hot water circuits. Today, almost all installations in Denmark are built with stainless steel and polymeric materials pipes. In many other European countries, copper pipes are still widely used, and the use of hot-dip galvanized steel pipes is decreasing. In some countries, including Poland, galvanized steel piping is still popular, and this paper presents an investigation of cold water galvanized steel premature piping failure. Corrosion failure of seam-welded galvanized steel cold water pipes was reported to occur just after 18–24 months in service, and, according to the information from the installer, S1 values determined in long-term measurements were below 0.5.

However, this paper presents an unusual case when only cold water galvanized steel pipes corroded in the same internal water supply system, while hot water pipes made of the same galvanized steel showed no signs of corrosion.

Experimental

Failed galvanized (S195T) steel pipes with 60.3 and 76.1 mm diameters were examined. A Foundry-Master (WAS) spectrometer was employed for the chemical analysis, as shown in Table 1, which also reports the relevant standard. Photographs showing the inside surfaces of the 2 pipes were taken. Zeiss Axiovert 200 MAT light microscope and a scanning electron microscope FEI INSPECT S50, equipped with energy-dispersive spectrometry (EDS), were used to study microstructure and microcomposition, especially of the inner surfaces of the pipes.

Table 1 Chemical analysis of the investigated pipes, and EN 10255 standard, in wt.%

Results

The chemical composition of the base steel as given in Table 1 meets the standard requirements for S195T steel. Typical macroscopic pictures of samples cut from the two perforated galvanized steel are shown in Figs. 1 and 2. The area marked in red in Fig. 2 was in close proximity to the screw connection pipe valve.

Fig. 1
figure 1

Macroscopic view of samples of the 60.3-mm pipe

Fig. 2
figure 2

Macroscopic view of samples of the 76.1-mm pipe

The microstructure of the base material of pipes is presented in Fig. 3 and is proper, typical for such steel grade (cross section near the pitting area). Metallographic examinations (not reported here) on transverse and longitudinal specimens did not reveal any metallurgical defects or other irregularities in the microstructure.

Fig. 3
figure 3

The microstructure of the base material: (a) 60.3-mm pipe, (b) 76.1-mm pipe

The tested galvanized steel pipe inner surface samples (pitting area) were clean and almost free of corrosion products (oxides). Figure 4 shows a scanning electron micrograph of the sample shown in Fig. 2b and shows that in this section of the pipe, near a yellow brass valve, pitting and shiny, silvery gray areas were observed in the vicinity of corrosive pits and in other examined sections. This demonstrates the purely galvanic nature of the formation of corrosion perforations in the studied pipe sections (so-called contact corrosion).

Fig. 4
figure 4

Surface morphology of the pitting area of Fig. 2b: (a) pit, (b) vicinity region

The galvanic nature of the formation of corrosion perforations was confirmed by EDS x-ray microanalysis; the results are shown in Figs. 5, 6, 7 and 8. In the area of pitting (Fig. 6), the analysis revealed the presence of elements contained in the steel, practically without the presence of zinc. Similarly, for the pit vicinity area, only trace zinc content was revealed. The thin layer, visible at the bottom right of the micrograph (Fig. 7), is a residue from the original galvanized layer (iron–zinc), while further away (right side of the micrograph), there are general corrosion products (iron oxides, Fig. 8).

Fig. 5
figure 5

The area of EDS microanalysis

Fig. 6
figure 6

The results of EDS microanalysis in the pit

Fig. 7
figure 7

The results of EDS microanalysis in the zinc layer residue

Fig. 8
figure 8

The results of EDS in the general corrosion area

Discussion

The bright, silvery gray areas present in the vicinity of the pits (Figs. 1, 2) on the inner surface of galvanized steel pipes were also observed by other authors [14], but were apparently not thoroughly examined. In [14], only macro-images of such areas were shown.

As shown in Fig. 2, pitting in the examined cold water galvanized steel pipes occurred only in close proximity to the screw connection pipe valve. According to information obtained from the installation user, the examined cold water pipes were installed with yellow, in contrast to the hot water galvanized steel pipes where the nickel-plated brass ball valves were installed.

The use of yellow brass valves in direct electric contact with the galvanized steel pipes is a significant installation error, and it was the cause of the premature corrosion failure of the cold water zinc-coated steel pipes. The phenomenon called contact corrosion (bimetallic corrosion) occurs when two different metals are attached to one another (in this case, galvanized steel and yellow brass) and contact an electrolyte (flowing water). This results in different electrode potentials in the two metals with respect to the electrolyte. The base metal (zinc layer on the steel) is transformed into an anode, and this leads to the accelerated corrosion of that metal and inhibits the corrosion of the other, more noble metal (yellow brass), which is transformed into a cathode. This is what happened in the cold water galvanized steel pipes in the failed water supply system. When mixed with brass, galvanized steel triggers dezincification, and it results in electrolytic action [9, 10].

Conclusion

Corrosion failure of two seam-welded galvanized steel cold water pipes, occurring just after 18–24 months in service, was investigated. According to the installation user, S1 values determined in long-term measurements were below 0.5 (results not reported here) which justified the application of galvanized steel pipes in this water supply system. Microscopic and microanalytical examinations showed that the cold water pipe failures were associated with the use of yellow brass valves in direct electric contact with the galvanized steel pipes. This conclusion is additionally supported by the lack of signs of corrosion in the same galvanized steel pipes in hot water installation, where nickel-plated ball valves were used.