KSME International Journal

, Volume 14, Issue 5, pp 537–546 | Cite as

Some aspects of experimental in-tube evaporation

  • Samchul Ha
Thermal Engineering · Fluid Engineering · Energy and Power Engineering

Abstract

The heat transfer characteristics of refrigerant-oil mixture for horizontal in-tube evaporator have been investigated experimentally. A smooth copper tube and a micro-fin tube with nominal 9.5 mm outer diameter and 1500 mm length were tested. For the pure refrigerant flow, the dependence of the axial heat transfer coefficient on quality was weak in the smooth tube, but in the micro-fin tube, the coefficients were 3 to 10 times greater as quality increases. Oil addition to pure refrigerant in the smooth tube altered the flow pattern dramatically at low mass fluxes, with a resultant enhancement of the wetting area by vigorous foaming. The heat transfer coefficients of the mixture for low and medium qualities were increased at low mass fluxes. In the micro-fin tube, however, the addition of oil deteriorates the local heat transfer performance for most of the quality range, except for low quality. The micro-fin tube consequently loses its advantage of high heat transfer performance for an oil fraction of 5%. Results are presented as plots of local heat transfer coefficient versus quality.

Key Words

Refrigerant-Oil Mixture In-Tube Evaporator Smooth Tube Micro-Fin Tube Heat Transfer Coefficient Mass Flux 

Nomenclature

De

Envelope diameter (mm)

Do

Outside diameter

f

Fin height (mm)

G

Mass flux (kg/(m2s))

q

Heat flux (kW/m2)

t

Tube thickness

Preview

Unable to display preview. Download preview PDF.

Unable to display preview. Download preview PDF.

References

  1. ASHRAE Standard, 1984, “Standards Method for Measurement of Proportion of Oil in Liquid Refrigerant” ASHRAE 41. 4Google Scholar
  2. Eckels, S. J. and Pate, M. B. 1991, “Evaporation and Condensation of HFC-134a and CFC-12 in a Smooth Tube and a Micro-fin Tube,”ASHRAE Trans., Vol. 97, pt. 2, pp. 71–81.Google Scholar
  3. Ha, S. 1992, “Heat Transfer Characteristics of Horizontal In-Tube Evaporation,” Ph. D. Thesis, Rensselaer Polytechnics Institute, Troy, NY.Google Scholar
  4. Ha, S. and Bergles, A. E. 1993a, “The Influence of Oil on Local Evaporation Heat Transfer Inside a Horizontal Micro-fin Tube,”ASHRAE Trans., Vol. 99, pt. 1, pp. 1244–1255.Google Scholar
  5. Ha, S. and Bergles, A. E. 1993b “Local Heat Transfer Characteristics of Horizontal In-Tube Evaporation,”Proc. 6th Int. Symp. Transport Phenomena, Seoul, Korea, Vol. 2, pp. 357–364.Google Scholar
  6. Ito, M., Kimura, H. and Senshu, T. 1977, “Development of High Efficiency Air-cooled Heat Exchanger,”Hitachi Review, Vol. 26, No. 10, pp. 323–326.Google Scholar
  7. Kandlikar, S. G. 1990, “A General Correlation for Saturated Two-Phase Flow Boiling Heat Transfer Inside Horizontal and Vertical Tubes,”J. Heat Transfer, Vol. 112, No. 1, pp. 219–228.CrossRefGoogle Scholar
  8. Kim, J-D., Yoon, J-I., Ku, H-G., 1997, “Dynamic Analysis of Evaporator Characteristics,”KSME Int. J., Vol. 11, No. 2, pp. 221–228.Google Scholar
  9. Kim, J. S., Nagata, K., Katsuta, M., Tomosugi, H., Kikuchi, K., & Horichi, T., 1988, “Influence of Oil on Refrigerant Evaporator Performance-1st Report: Local Heat Transfer Coefficients,”Trans. JAR, Vol. 5, No. 1, pp. 89–96.Google Scholar
  10. Kimura, H. and Ito, M. 1981, “Evaporating Heat Transfer in Horizontal Internal Spiral-Grooved Tubes in the Region of Low Flow Rates,”JSME Int. J., Vol. 24, No. 195, pp. 1602–1607.Google Scholar
  11. Manwell, S. P. and Bergles, A. E. 1990, “Gas-Liquid Flow Pattern in Refrigerant-Oil Mixtures,”ASHRAE Trans., Vol. 96, pt. 2, pp. 456–464.Google Scholar
  12. Schlager, L. M., Bergles, A. E. and Pate, M. B. 1988, “Evaporation and Condensation of Refrigerant-Oil Mixtures in a Smooth Tube and a Micro-fin Tube,”ASHRAE Trans., Vol. 94, pt. 1, pp. 149–166.Google Scholar
  13. Schlager, L. M., Bergles, A. E., and Pate, M. B. 1989, “A Comparison of 150 and 300 SUS Oil Effects on Refrigerant Evaporation and Condensation in a Smooth Tube and a Micro-fin Tube,”ASHRAE Trans., Vol. 95, pt. 1, pp. 387–397.Google Scholar
  14. Tatsumi, A, Oizumi, K., Hayashi, M., and Ito, M., 1982, “Application of Inner Groove Tubes to Air Conditioners,”Hitachi Cable Review, Vol. 32, No. 1, pp. 55–60.Google Scholar
  15. Torikoshi, K., Kawabata, K., and Ebisu, T., 1992, “Heat Transfer and Pressure Drop Characteristics of HFC-134a in a Horizontal Heat Transfer Tube,”Proc. Int. Refrigeration Conf., Purdue, July, Vol. 1, pp. 167–176.Google Scholar
  16. Torikoshi, K. and Ebisu, T. 1993, “Heat Transfer and Pressure Drop Characteristics of R-134a, R-32, and a Mixture of R-32/R-134a inside a Horizontal Tube,”ASHRAE Trans., Vol. 99, pp. 350–356.Google Scholar
  17. Yoshida, S., Matsunaga, T., Hong, H-P., and Nishikawa, K. 1988, “Heat Transfer Enhancement in Horizontal, Spirally Grooved Evaporator Tubes,”JSME Int. J., Vol. 31, No. 3, pp. 505–512.Google Scholar

Copyright information

© The Korean Society of Mechanical Engineers (KSME) 2000

Authors and Affiliations

  1. 1.LG Electronics Inc.KyungnamKorea

Personalised recommendations