Three-phase fault direction identification method for outgoing transmission line of DFIG-based wind farms

  • Zhanfeng FAN
  • Guobing SONG
  • Xiaoning KANG
  • Jisi TANG
  • Xiaobo WANG
Open Access
Article
  • 152 Downloads

Abstract

Doubly-fed induction generator (DFIG)-based wind farm has the characteristic of transient fault with low voltage ride through (LVRT) capability. A new three-phase fault direction identification method for the outgoing transmission line of the wind farm is presented. The ability of the new directional relay to differentiate between a three-phase fault in one direction or the other is obtained by using the increment of phase angle difference between the memory voltage signal and the fault current signal within a certain time, and using the amplitude variation of the fault current. It can be inferred that the fault current is supplied by the wind farm whether the phase angle differs or the current amplitude varies considerably. Different fault locations at the outgoing transmission line have been simulated by PSCAD/EMTDC to evaluate the reliability and sensitivity of the proposed technique. Results show that the new directional relay is of faster response when a three-phase fault occurs at the outgoing transmission line of a DFIG-based wind farm.

Keywords

Wind farm Doubly-fed induction generator (DFIG) Directional relay Outgoing transmission line 

1 Introduction

With the rapid development of wind generation technology and the increasing growth of wind power capacity in power systems, large-scale wind farms have a great impact on relay protection [1, 2]. As the electricity collecting element, the outgoing transmission line is quite important for normal operation of a wind farm, especially in a doubly-fed induction generator (DFIG)-based wind farm, which is a widely applied type [3, 4]. Thus it is necessary to find a reliable protection scheme for such transmission lines. The directional relay is one of the most important protection elements. A traditional fault component-based directional relay is extensively used in practice because of its simple structure, fast response, and good adaptability to load, fault type and transition resistance. However, the fault characteristics of a wind farm are different from those of conventional power systems [5, 6]. Because of the input of a crowbar protection circuit, the main frequency of the short circuit current fed by a doubly-fed wind farm with a capacity of low voltage ride through (LVRT) will be the rotating frequency of the wind turbine before the fault, and it may no longer maintain the power frequency (50 Hz). This may considerably impact on the performance of the traditional directional relay which compares the phase angles of current and voltage.

It is necessary to study a new directional relay which is adaptable to the outgoing transmission line of the wind farm. Given the difference of phase angles between fault and load current when a fault occurs forward and backward [7], a direction identification approach has been proposed. However, the method has the adaptability problem in a wind power system because of the fast variation of the load current. Two kinds of directional relays based on a sequence component are presented in [8]: one calculates the ratio of the negative sequence component to the zero sequence component and identifies direction by comparing the ratio with a statistical boundary value; the other compares the values of the fifth harmonic of the zero sequence component with the positive sequence component to determine the fault direction. Both directional relays work well under ideal conditions. However, rich high order harmonics and non-periodic components during a fault in a wind power system will reduce the precision of this method. A new method for discriminating a directional element is proposed in [9]. This method applies the principle that the transient potential of a DFIG has inertia for a short time after a fault. However, due to the short duration of the inertia of the equivalent transient electromotive force (EMF) of the DFIG, this method will fail if the protection cannot effectively determine the fault direction during this period. In [10], a fault current classification method is proposed, and the fault direction is identified according to the difference of fault current waveforms. However, it needs to add frequency tracking links, and the action time for the protection is longer.

This paper purposes a faster direction identification method for the condition that the traditional directional relay cannot identify the fault direction accurately when a three-phase fault occurs. The new method mainly utilizes the characteristics that the short circuit current of the forward fault is usually a non-power frequency attenuation AC component, while the short circuit current of the backward fault is a power-frequency AC component. If the phase angle difference of the fault current is large after a period of failure, it is considered to be a positive direction export fault; if the phase angle difference is small but the amplitude difference is large, it is still considered as a forward outlet fault; if the phase angle difference and amplitude difference of the fault current calculation are relatively small, it is considered to be a reverse outlet fault of the outgoing line. A large-scale wind farm model is established in PSCAD environment to verify the proposed protection. Simulation results show that the fault direction can be accurately identified on both sides of the line when a three-phase fault occurs.

2 Adaptability analysis of traditional directional relay to DFIG-based wind farm

When the voltage measured by a relay drops only a little during a fault, the positive sequence voltage prior the fault is memorized and adopted as the polarized voltage for traditional directional relay [7], as shown in (1):
$$- 90^\circ < {\text{arg (}}\frac{{ - \dot{U}_{f1} }}{{\dot{U}_{m} - \dot{I}_{m} Z_{set} }}) < 90^\circ$$
(1)
where \(\dot{U}_{f1}\) is the positive sequence voltage prior to the fault, \(\dot{U}_{m}\) and \(\dot{I}_{m}\) are the voltage and current respectively measured by the relay, and \(Z_{set}\) is the setting impedance.
When the positive sequence voltage drops below 20% of its pre-fault value, a positive sequence voltage polarized phase comparison circle is generally used for direction identification, with the memorized positive sequence voltage adopted as the polarized voltage. The operational equation is shown as in (2).
$$- 90^\circ < \text{a}{\text{rg (}}\frac{{ - \dot{U}_{po1} }}{{\dot{U}_{m} - \dot{I}Z_{set} }}) < 90^\circ$$
(2)
where \(\dot{U}_{po1}\) is the memorized voltage.
In order to test the function of the traditional directional relay of the outgoing transmission line in a wind farm, the model of a DFIG-based wind farm shown in Fig. 1 is built and simulated in PSCAD/EMTDC. The installed capacity of the wind farm is 300 MW. Through a package transformer, DFIG, with a terminal voltage of 0.69 kV and a capacity of 5 MW, is connected to a collecting line (35 kV). With the main transformer, the collecting lines are integrated to an outgoing transmission line (220 kV). Thus the wind farm is connected to a 220 kV bus, and the electrical energy is delivered to the power system. The parameters of the simulated model are listed in Table 1 and Table 2.
Fig. 1

System topology of DFIG-based wind farm

Table 1

Parameters of DFIG-based wind farm

Unit

Parameter

Value

Wind turbine

Rated capacity (MW)

5

Rated voltage (kV)

0.69

Stator resistance (p.u.)

0.00756

Stator leakage resistance (p.u.)

0.1425

Rotor resistance (p.u.)

0.00533

Rotor leakage resistance (p.u.)

0.1425

Excitation reactance (p.u.)

2.1767

Box transformer

Rated capacity (MW)

7.5

Rated voltage (kV)

0.69/35

Positive sequence leakage reactance (p.u.)

0.0895

No-load loss (p.u.)

0.00035

Copper consumption (p.u.)

0.0094

Table 2

Parameters of the main transformer of the wind farm and the outgoing transmission line

Unit

Parameter

Value

Main transformer

Rated capacity (MW)

450

Rated voltage (kV)

35/220

Positive sequence leakage reactance (p.u.)

0.0895

No-load loss (p.u.)

0.00035

Copper consumption (p.u.)

0.0094

Outgoing transmission line

Positive sequence resistance of unit length (Ω/km)

0.019

Positive sequence reactance of unit length (Ω/km)

0.2463

Unit length positive sequence capacitor (nF/km)

14.8024

Unit length zero sequence resistance (Ω/km)

0.2079

Zero sequence reactance of unit length (Ω/km)

0.7758

Zero sequence capacitance per unit length (nF/km)

8.703

Length of transmission line (km)

100

Figure 2 shows the phase angle comparison between the memory voltage and the measured voltage by directional relay when a three-phase fault occurs at the middle point of the outgoing transmission line. Memory voltage is taken as reference voltage.
Fig. 2

Phase angle comparison between memory voltage and measured voltage

As shown in Fig. 2, when a symmetrical short circuit occurs in the forward direction of the wind-side directional relay, the phase angle of the terminal voltage of the wind farm periodically fluctuates. With the LVRT capability, DFIGs switch on a crowbar to protect the converter during the fault when DFIGs can be seen as an induction motor, which leads to a change of frequency. Therefore, a traditional directional relay cannot reliably identify the fault direction. On the other hand, the grid-side directional relay of the outgoing transmission line performs well in this situation. Further simulation shows that if the fault current measured by the directional relay is provided by the power system, the directional relay identifies the fault direction correctly and if the current measured by the directional relay is supplied by the DFIG-based wind farm, the directional relay cannot correctly identify the fault direction.

3 Fault characteristics of the outgoing line of a DFIG-based wind farm

The fault current of a crowbar-protected DFIG has three components: ① decaying DC component, ② decaying AC component at the rotating frequency of the rotor, ③ steady state fundamental frequency component [8]. Among them, the three phase currents component at the rotating frequency of the rotor can be described as (3):
$$\left\{ {\begin{array}{*{20}l} {i_{{sa\omega_{r} }} (t) = \text{e}^{{ - t/\tau_{r} }} a_{\alpha 1} \sin \omega_{r} t{ + }\text{e}^{{ - t/\tau_{r} }} a_{\alpha 2} \cos \omega_{r} t} \hfill \\ {i_{{sb\omega_{r} }} (t) = \text{e}^{{ - t/\tau_{r} }} a_{\alpha 1} \sin (\omega_{r} t - 2\uppi/3) + \text{e}^{{ - t/\tau_{r} }} a_{\alpha 2} \cos(\omega_{r} t - 2\uppi/3)} \hfill \\ {i_{{sc\omega_{r} }} (t) = \text{e}^{{ - t/\tau_{r} }} a_{\alpha 1} \sin (\omega_{r} t + 2\uppi/3) + \text{e}^{{ - t/\tau_{r} }} a_{\alpha 2} \cos(\omega_{r} t + 2\uppi/3)} \hfill \\ \end{array} } \right.$$
(3)
where \(a_{\alpha 1}\), \(a_{\alpha 2}\) are the intrinsic parameters of the DFIG; \(\tau_{r}\) is the equivalent time constant of the rotor winding; and \(\omega_{r}\) is the angle frequency of the rotor.

3.1 Case 1: rotating frequency of rotor far away from power frequency

When a three-phase fault occurs at the outgoing transmission line of the wind farm, the terminal voltage of the DFIG significantly drops. The memory voltage, which is taken as the polarized voltage, is a steady-state quantity at the power frequency, while the component at the rotating frequency of the rotor takes the biggest part of the stator current [11]. According to (3), the expression of the BC phase-to-phase fault current can be derived as:
$$i_{bc} = I_{bc} \sin (\omega_{r} t + \theta_{1} )$$
(4)
The BC phase-to-phase memory voltage (positive sequence) is described as:
$$u_{bc1} = U_{bc1} \sin (\omega_{1} t + \theta_{2} )$$
(5)
where Ibc, Ubc1, θ1 and θ2 are the amplitudes and initial phase angles of the fault current and memory voltage, respectively.
To extract the real and imaginary parts from the measured data, full-cycle Fourier algorithm is applied. For example, real and imaginary parts of the voltage are calculated by (6) and (7), respectively.
$$U_{R} = \frac{2}{{T_{1} }}\int_{t}^{{t + T_{1} }} {u_{bc1} \sin (\omega_{1} t)} {\text{d}}t$$
(6)
$$U_{I} = \frac{2}{{T_{1} }}\int_{t}^{{t + T_{1} }} {u_{bc1} \cos(\omega_{1} t)} {\text{d}}t$$
(7)
The phase difference between the voltage and stator fault current is introduced as:
$$\theta = { \arg }(\frac{{\dot{U}_{bc1} }}{{\dot{I}_{bc} }})$$
(8)
According to (4)–(8), the expression of \(\theta\) can be calculated as:
$$\begin{aligned} \theta = \theta_{1} - \arctan \frac{{(\omega_{r} + \omega_{1} )\sin ((\omega_{r} - \omega_{1} )t + \frac{{\omega_{r} }}{{\omega_{1} }}\uppi + \theta_{2} )}}{{(\omega_{r} + \omega_{1} )\cos((\omega_{r} - \omega_{1} )t + \frac{{\omega_{r} }}{{\omega_{1} }}\uppi + \theta_{2} )}} \to \hfill \\ {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} \leftarrow \frac{{(\omega_{r} - \omega_{1} )\sin ((\omega_{r} + \omega_{1} )t + \frac{{\omega_{r} }}{{\omega_{1} }}\uppi + \theta_{2} )}}{{(\omega_{r} - \omega_{1} )\cos ((\omega_{r} + \omega_{1} )t + \frac{{\omega_{r} }}{{\omega_{1} }}\uppi + \theta_{2} )}}{\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} {\kern 1pt} \hfill \\ \end{aligned}$$
(9)
\(\Delta \theta\) is defined as the increment of the phase angle difference between the memory voltage and fault current, which is calculated as:
$$\Delta \theta = \hbox{max} (\theta ) - \hbox{min} (\theta )$$
(10)
where \(\hbox{min} (\theta )\), \(\hbox{max} (\theta )\) is the maximum and the minimum value of the phase angle difference between memory voltage and fault current respectively. This is measured by the directional relay of wind farm side during the fault occurring for 20 ms to 30 ms. The relationship of \(\Delta \theta\) and the rotating frequency of the rotor is shown in Fig. 3.
Fig. 3

Relationship between increment of phase angle difference ∆θ and rotational frequency prior to the fault

According to Fig. 3, larger deviation of the rotating frequency from the power frequency leads to larger \(\Delta \theta\). When the rotating frequency equals the power frequency, \(\Delta \theta\) is 0. At the same time, the fault current supplied by the power system has two components, of which the steady state current takes the larger part, as shown in (11).
$$i_{f} (t) = I_{m} \sin (\omega_{0} t + \theta_{2} ) + I_{m} \sin (\theta_{2} )\text{e}^{ - t/\tau }$$
(11)
where \(I_{m}\) is the amplitude of the current supplied by the synchronous generator and \(\tau\) is the decaying time constant of the synchronous generator. \(\tau\) ranges from 1 ms to 100 ms while \(\theta_{2}\) goes from \(0^{ \circ }\) to \(180^{ \circ }\). So the \(\Delta \theta\) calculated by the directional relay on the grid side ranges from 0° to 2.63°.

Based on this characteristic, the threshold of \(\Delta \theta\) can be set as \(\Delta \theta_{set} = 8^\circ\). When \(\Delta \theta > \Delta \theta_{set}\), it means that the fault current is supplied by the DFIG and thereby the fault direction can be identified by the directional relay. When \(\Delta \theta < \Delta \theta_{set}\), there are two possibilities: ① the fault current is provided by the DFIG with rotating frequency near the power frequency; ② the fault current is supplied by the power system. Thus further criteria are needed to identify the direction.

3.2 Case 2: rotating frequency of rotor close to power frequency

According to (9) and (10), when the rotating frequency of the rotor ranges from 47.83 Hz to 52.17 Hz, \(\Delta \theta\) calculated by the directional relay would be less than 8°. On the other hand, the fault current supplied by the wind farm decays quickly while the fault current supplied by the regular power system stays relatively stable. A further algorithm on quantity amplitude shows that the maximum error is 3.38% in this frequency range (47.83 Hz to 52.17 Hz). Therefore, when \(\Delta \theta\) is small enough, the decay rate of the fault current amplitude calculated by a Fourier algorithm can be utilized as a complementary criterion for the directional relay.

When the voltage seriously drops during a three-phase short circuit, the steady state fundamental frequency component of the fault current supplied by the wind farm can be ignored. And the fault current has only a decaying AC component at the rotating frequency of the rotor [9]. The fault current of the wind farm is:
$$i_{k} (t) = I_{m} \text{e}^{{ - {t \mathord{\left/ {\vphantom {t {\tau_{r}^{{}} }}} \right. \kern-0pt} {\tau_{r}^{{}} }}}} \cos (\omega_{r} t + \alpha_{1} )$$
(12)

The amplitude of the decaying AC component decays exponentially.

In order to reflect the amplitude variation of the fault current, the current decay rate d is defined as:
$$d = \frac{{\left| {I_{k} (t_{0} ) - I_{k} (t_{T/2} )} \right|}}{{I_{k} (t_{0} )}} \times 100\%$$
(13)
where \(I_{k} (t_{0} )\) and \(I_{k} (t_{T/2} )\) are current amplitudes at the moment of fault occurrence and half a sampling cycle of the full-cycle Fourier algorithm, respectively.
During a fault, the damping rate of the decaying AC component is determined by the rotor’s decay time constant which can be expressed as [10]:
$$\tau_{r} = \frac{{X_{r} + \frac{{(X_{s} + X_{e} )X_{m} }}{{X_{s} + X_{e} + X_{m} }}}}{{\omega_{0} (R_{r} + R_{cb} )}}$$
(14)
where \(X_{s}\), \(X_{r}\) are the leakage reactances of the stator and rotor windings respectively; \(R_{r}\) is the rotor resistance; \(X_{m}\) is the magnetizing reactance; \(X_{e}\) is the equivalent reactance from the DFIG’s terminal and the fault point; \(R_{cb}\) is the crowbar resistance; and \(\omega_{0}\) is the angular frequency corresponding to the power frequency.

The current decay rate is calculated when a three-phase fault occurs at the outgoing line in a DFIG-based wind farm with classical parameters which can be found in [12, 13, 14, 15, 16]. The value of the crowbar resistance normally ranges from 10\(R_{r}\) to 30\(R_{r}\) [17, 18]. According to (14), the decay time constant varies from 0.3 ms to 3.19 ms. Thus the decay rate of the current varies from 26.91% to 96.43%.

If the fault current is supplied by a regular power system, according to (11), the decay rate of current is calculated in the range of [0%, 10.51%].

To sum up, based on the calculated results, the threshold value of criterion \(d_{set}\) can be set at 20%.

4 New criterion for directional relay

Based on the above analysis, the principle of the new criterion for the directional relay is based on two quantities: the increment of phase angle difference between the fault current and memory voltage \(\Delta \theta\) and the decay rate of the fault current d. If \(\Delta \theta\) calculated by directional relay is larger than \(\Delta \theta_{set} = 8^\circ\), it means that the fault current is provided by the DFIG-based wind farm. Otherwise, when \(\Delta \theta\) is less than \(\Delta \theta_{set}\), the supplier of the fault current can be determined with the help of d. If d is larger than \(d_{set} = 20\%\), the DFIG wind farm supplies the fault current; otherwise, the fault current is provided by the power system. According to the provider of the fault current, it is easy to identify the direction of the fault. The flowcharts of the proposed direction identification criterion for the directional relays at two ends of the outgoing transmission line are shown in Fig. 4.
Fig. 4

Flowchart of the proposed direction identification criterion

5 Simulation and verification

This section will test the performance of the direction identification criterion proposed in last section.

5.1 Analysis of influencing factors

Different speeds of a wind turbine will affect the value of measured \(\Delta \theta\). A smaller crowbar resistor and a shorter outgoing line will cause a larger stator time constant, which will influence the current decay rate d. The wind farm integration shown in Fig. 1 is built, and different cases are simulated to analyze the effect of these three factors on the proposed directional relay criterion.

5.1.1 Rotating frequency of DFIG

The experimental relation between the calculated \(\Delta \theta\) and the rotating frequency of the rotor is shown in Fig. 5. When the rotating frequency is close to the power frequency, \(\Delta \theta\) is relatively small. When the rotating frequency ranges from 45.3 Hz to 53.8 Hz, the value of \(\Delta \theta\) is less than 8°, which basically coincides with the theoretical analysis shown in Fig. 3. The value of \(\Delta \theta\) would not decrease to 0° when the rotating frequency equals the power frequency because of the calculation error caused by the decaying amplitude of the fault current at the rotating frequency.
Fig. 5

Experimental relationship between ∆θ and rotor’s rotating frequency

5.1.2 Value of crowbar resistance

When a three-phase fault occurs at the end of the outgoing transmission line on the wind farm side, the amplitude of the fault current has been calculated with crowbar resistance set at 10Rr, 20Rr and 30Rr.

As shown in Fig. 6, a larger crowbar resistance results in a larger decay rate of the current amplitude. Figure 7 depicts the relation between the current decay rate and crowbar resistance. It can be seen that with the increasing crowbar value, the current decay rate rises considerably from 53.04% to 87.40%.
Fig. 6

Amplitude of current with different crowbar resistances

Fig. 7

Relation between current decay rate and crowbar resistance

5.1.3 Length of outgoing transmission line

The relation between the current decay rate and the length of the outgoing transmission line is shown in Fig. 8. It can be seen that the current decay rate has a slight growth with length increasing length of the outgoing transmission line.
Fig. 8

Relation between current decay rate and the length of the outgoing transmission line

5.2 Simulation of directional relay performance

The simulation model of a DFIG-based wind farm shown in Fig. 1 has been built in PSCAD/EMTDC to test the performance of the proposed directional relay criterion. The value of \(\theta\) recorded by the wind farm side directional relay is shown in Figs. 9 and 10 during a forward fault and a backward fault respectively. The rotating frequency of the rotor is 0.8 times of the power frequency.
Fig. 9

Value of θ recorded by directional relay on wind farm side when a forward fault occurs at 50 km away from the relay location

Fig. 10

Value of θ recorded by directional relay on wind farm side when a backward fault occurs near the relay location

In Fig. 9, there is \(\Delta \theta\) = 21.3°, which is larger than 8°. Thus the directional relay detects a forward fault. In Fig. 10, \(\Delta \theta\) =  0.33°, which is less than 8°. Thus the decay rate of the current amplitude is needed to identify the fault direction. The amplitude of the fault current is shown in Fig. 11 where d=1.41% is less than 20%. Therefore, the directional relay detects a backward fault.
Fig. 11

Amplitude of fault current measured by directional relay on wind farm side when a backward fault occurs near the relay location

The value of θ recorded by the wind farm side directional relay is shown in Figs. 12 and 13 during a forward and backward fault respectively. The rotating frequency of the rotor is very close to the power frequency.
Fig. 12

Value of θ recorded by directional relay on wind farm side when a forward fault occurs at 50 km away from relay location (under power frequency)

Fig. 13

Value of θ recorded by directional relay on wind farm side when a backward fault occurs near the relay location (under power frequency)

In Fig. 12, \(\Delta \theta\) = 7.17°, which is less than 8°. So the decay rate of the current amplitude is needed to identify the fault direction. The amplitude of the fault current is shown in Fig. 14, where d = 33.18% is larger than 20%. Thus the directional relay detects a forward fault.
Fig. 14

Amplitude of fault current measured by directional relay on wind farm side when a forward fault occurs near relay location

In Fig. 13, \(\Delta \theta\) = 0.30°, which is also less than 8°. So the decay rate of current amplitude also is needed. The amplitude of the fault current is shown in Fig. 15, where d = 0.60% is less than 20%. Therefore, the directional relay detects a backward fault.
Fig. 15

Amplitude of fault current measured by directional relay on wind farm side when a backward fault occurs near relay location (under power frequency)

Simulations under different conditions are completed and the results are shown in Tables 3 and 4.
Table 3

Performance of new directional relay on wind farm side under different conditions

Condition

Rotating speed of rotor (p.u)

Results

Reaction time (ms)

Backward fault at the terminal

0.8

Backward

30

1.0

Backward

30

1.2

Backward

30

Fault point away from relay 0 km

0.8

Forward

30

1.0

Forward

30

1.2

Forward

30

Fault point away from relay 40 km

0.8

Forward

30

1.0

Forward

30

1.2

Forward

30

Fault point away from relay 100 km

0.8

Forward

30

1.0

Forward

30

1.2

Forward

30

Table 4

Performance of new directional relay on system side under different conditions

Condition

Rotating speed of rotor (p.u)

Results

Reaction time (ms)

Backward fault at the terminal

1.2

Backward

30

1.0

Backward

30

0.8

Backward

30

Fault point away from relay 0 km

0.8

Forward

30

1.0

Forward

30

1.2

Forward

30

Fault point away from relay 40 km

0.8

Forward

30

1.0

Forward

30

1.2

Forward

30

Fault point away from relay 100 km

0.8

Forward

30

1.0

Forward

30

1.2

Forward

30

It can be seen that with the new direction identification criterion, the directional relays on both sides of the outgoing transmission line of the DFIG-based wind farm can quickly provide a correct fault direction. The identification process takes just 30 ms.

Compared with the direction identification method given in [11], the new criterion proposed in this paper has the following advantages:
  1. 1)

    At the moment when the three-phase fault occurs, the frequency of the fault current provided by the DFIG deviates from the power frequency immediately. Frequency tracking according to [11] consumes more time. The directional relay presented in this paper only needs to calculate the increment of phase angle difference \(\Delta \theta\) and the decay rate of the fault current d, which avoids frequency tracking and is time saving.

     
  2. 2)

    The directional relay in [11] takes 40 ms to detect the fault direction while the new relay only needs 30 ms.

     
  3. 3)

    This paper comes up with the new criterion based on \(\Delta \theta\) and the comparison of decay rate of current between the DFIG-based wind farm and a regular power system. Reference [11] only uses the current decay rate of a regular power system.

     

6 Conclusion

This paper presents a new direction identification method for a three phase short circuit in the outgoing transnmission line of a DFIG-based wind farm with the following characteristics:
  1. 1)

    When a three-phase fault occurs in the outlet of the wind farm, the input of the crowbar circuit makes the characteristic of the short circuit current of the DFIG quite different from that of the traditional synchronous machine, which eventually leads to malfunction or rejection of the traditional directional protection elements using the memory voltage as the polarization voltage.

     
  2. 2)

    When the three-phase short circuit fault occurs in the outlet of the transmission line, and the rotating frequency of the DFIG is close to the power frequency, the phase angle calculated by the short circuit current provided by the fan side varies linearly with time. When the rotating frequency of the fan is far away from the power-frequency, the calculation of the circuit current of DFIG is more stable, but the calculated current amplitude will fade with time. When a three-phase short-circuit backward fault occurs at the outlet of the transmission line, the phase angle and amplitude calculated by the short-circuit current provided by the system side are relatively stable.

     
  3. 3)

    According to the above fault characteristics, a new direction element criterion for the outgoing transmission line of the wind farm is put forward. If the phase angle difference of the fault current is large after a period of failure, it is considered to be a positive direction export fault; if the phase angle difference is small but the amplitude difference is large, it is still considered as a forward outlet fault; If the phase angle difference and amplitude difference of the fault current calculation are relatively small, it is considered to be the reverse outlet fault of the outgoing transmission line.

     
  4. 4)

    Simulation results show that, when the new direction element criterion is adopted, the fault direction can be correctly identified when three-phase faults occur in the forward and backward directions of the outgoing transmission line, and are not affected by factors such as the rotating frequency of the fan, the resistance value of the crowbar and the length of the line.

     

Notes

Acknowledgment

This work was supported by National Basic Research Program of China (No. 2012CB215105).

References

  1. [1]
    Pradhan AK, Gza J (2007) Adaptive distance relay setting for lines connecting wind farms. IEEE Trans Energy Convers 22(1):289–299CrossRefGoogle Scholar
  2. [2]
    Zhang BH, Guo DY, Wang J et al (2012) Configuration, cooperation and existing problems of wind farm relay protection. In: Proceedings of 2012 11th international conference on environment and electrical engineering (EEEIC), Venice, Italy, 18–25 May 2012, 5 ppGoogle Scholar
  3. [3]
    Viraj PM, Rama R (2008) Impact of distributed generation on distance protection performance—a review. In: Proceedings of 2008 IEEE PES general meeting, Pittsburgh, USA, 20–24 July 2008, 7 ppGoogle Scholar
  4. [4]
    Maryam K, Hosein KK (2011) Effect of wind turbines equipped with doubly-fed induction generators on distance protection. In: Proceedings of 2011 international conference on advanced power system automation and protection (APAP), Beijing, China, 16–20 October 2011, 5 ppGoogle Scholar
  5. [5]
    Li W, Pupu C, Xiaodong L et al (2018) Modeling of complete fault ride-through processes for DFIG-based wind turbines. Renew Energy 118:1001–1014CrossRefGoogle Scholar
  6. [6]
    Simon DR, Paula SP, Johan D (2010) Impact of wind turbines equipped with doubly-fed induction generators on distance relaying. In: Proceedings of 2010 IEEE PES general meeting, Providence, USA, 25–29 July 2010, 6 ppGoogle Scholar
  7. [7]
    Eissa M (2013) Current directional protection technique based on polarizing current. Int J Electr Power Energy Syst 44(1):488–494MathSciNetCrossRefGoogle Scholar
  8. [8]
    Petit M, Le PX, Garcia SL (2010) Directional relays without voltage sensors for distribution networks with distributed generation: use of symmetrical components. Electr Power Syst Res 80(10):1222–1228CrossRefGoogle Scholar
  9. [9]
    Yu C, Minghao W, Xianggen Y et al (2018) Distance protection for transmission lines of DFIG-based wind power integration system. Int J Electr Power Energy Syst 100:438–448CrossRefGoogle Scholar
  10. [10]
    Ali H, Maher AA, Ehab FE (2014) Three-phase fault direction identification for distribution systems with DFIG-based wind DG. IEEE Trans Sustain Energy 5(3):747–756CrossRefGoogle Scholar
  11. [11]
    Ali H, Maher AA, Ehab FE (2014) Distance protection of lines connected to induction generator-based wind farms during balanced faults. IEEE Trans Sustain Energy 5(4):1193–1203CrossRefGoogle Scholar
  12. [12]
    Qinhao L, Yongjun Z, Weipeng Y et al (2012) A study on influence of wind power on positive sequence voltage polarized impedance relay. In: Proceedings of 2012 IEEE power engineering and automation conference (PEAM), Wuhan, China, 14–16 September 2012, 4 ppGoogle Scholar
  13. [13]
    Kong X, Zhang Z (2014) Fault current study of wind turbine driven DFIG with crowbar protection. Elektrotehniški Vestnik 81(1–2):57–63Google Scholar
  14. [14]
    Yue M, Xingying C, Kun Y et al (2014) Analysis of short circuit current of DFIG-based wind generation system under different types of short circuits. Proc CSU-EPSA 26(2):60–65Google Scholar
  15. [15]
    Mostafa K, Xiaoning K, Guobing S et al (2015) Modeling and fault analysis of doubly fed induction generators for Gansu wind farm application. Can J Electr Comput Eng 38(1):52–64CrossRefGoogle Scholar
  16. [16]
    We ZP, Zheng T, Li J (2013) Short circuit current analysis of DFIG with crowbar under unsymmetrical grid fault. In: Proceedings of 2013 2nd renewable power generation conference (RPG), Beijing, China, 9–11 September 2013, 4 ppGoogle Scholar
  17. [17]
    Jiangbing H, Dan S, Yikang H et al (2006) Modeling and control of DFIG wind energy generation system under grid voltage dip. Autom Electric Power Syst 30(8):21–26Google Scholar
  18. [18]
    Lie X, Cartwright P (2006) Direct active and reactive power control of DFIG for wind energy generation. IEEE Trans Energy Convers 21(3):750–758CrossRefGoogle Scholar

Copyright information

© The Author(s) 2018

Open AccessThis article is distributed under the terms of the Creative Commons Attribution 4.0 International License (http://creativecommons.org/licenses/by/4.0/), which permits unrestricted use, distribution, and reproduction in any medium, provided you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons license, and indicate if changes were made.