Analysis of district cooling system with chilled water thermal storage in hot summer and cold winter area of China

  • Lun ZhangEmail author
  • Jun Jing
  • Mengfan Duan
  • Mingyang Qian
  • Da Yan
  • Xiaosong Zhang
Research Article
  • 2 Downloads

Abstract

A typical district cooling system (DCS) with a chilled water storage system is analyzed in hot summer and cold winter area in China. An analysis method concerning operation modes is proposed based on measured data, which is obtained by long term monitoring and on-site measurements of cooling season. The DCS operates at partial load for a large proportion of the cooling time; in particular, the partial-load rate (PLR) can be less than 25% for more than 50% of the total cooling season. In the night, PLR reaches 5% of the peak load. Thus, it is critical to achieve efficient operation under partial-load conditions of the DCS. Installation of chilled water thermal storage presents a solution to improve the working condition of the DCS and chillers. From the beginning to the end of the cooling season, the DCS operation can be summarized by typical operation modes according to cooling demand and chiller operation. For each mode, the base-load chiller operated at a high-load rate, with an average value of 0.88, and the coefficient of performance (COP) remained in a small range, between 4.2 and 5.2. The average energy efficiency ratio (EER) of the DCS for the cooling season was 3.65 and 3.81 for Years A and B, respectively. With respect to the economics, chillers used 90.2% of off-peak electricity, at only half the price of peak electricity.

Keywords

district cooling system thermal storage energy performance load characteristics operation mode 

List of symbols

cp

equivalent specific heat of water at constant pressure (J/(kg·K))

COP

coefficient of performance (—)

EER

energy efficiency ratio (—)

P

power input (kW)

PLR

partial-load rate (%)

Q

heat flow (kW)

Qd

daily cooling demand (MWh)

Qh

hourly cooling demand (MWh)

T

temperature (°C)

UR

unbalance rate (%)

G

volume flow rate of water (m3/h)

ρ

density of water (kg/m3)

φ

load rate of chiller (—)

Subscripts

con

condenser

eva

evaporator

wp

water pump

Preview

Unable to display preview. Download preview PDF.

Unable to display preview. Download preview PDF.

Notes

Acknowledgements

This study was supported by the China National Key R&D Program (No. 2016YFC0700100).

References

  1. Building Energy Conservation Research Center of Tsinghua University (2009). 2009 Annual Report on China Building Energy Efficiency. Beijing: China Architecture and Building Press. (in Chinese)Google Scholar
  2. Abou-Ziyan HZ, Alajmi AF (2014). Effect of load-sharing operation strategy on the aggregate performance of existed multiple-chiller systems. Applied Energy, 135: 329–338.CrossRefGoogle Scholar
  3. Baetens R, Coninck RD, Jorissen F, Picard D, Helsen L, Saelens D (2015). OpenIDEAS—An open framework for integrated district energy simulations. In: Proceeding of the 14th International IBPSA Building Simulation Conference, Hyderabad, India, pp. 347–354.Google Scholar
  4. Bergero FM, Casella F, Kofman E, Fernández J (2018). On the efficiency of quantization-based integration methods for building simulation. Building Simulation, 11: 405–418.CrossRefGoogle Scholar
  5. Brum M, Erickson P, Jenkins B, Kornbluth K (2015). A comparative study of district and individual energy systems providing electrical-based heating, cooling, and domestic hot water to a low-energy use residential community. Energy and Buildings, 92: 306–312.CrossRefGoogle Scholar
  6. Chan ALS, Hanby VI, Chow TT (2007). Optimization of distribution piping network in district cooling system using genetic algorithm with local search. Energy Conversion and Management, 48: 2622–2629.CrossRefGoogle Scholar
  7. Chow TT, Au WH, Yau R, Cheng V, Chan A, Fong KF (2004a). Applying district-cooling technology in Hong Kong. Applied Energy, 79: 275–289.CrossRefGoogle Scholar
  8. Chow TT, Chan ALS, Song CL (2004b). Building-mix optimization in district cooling system implementation. Applied Energy, 77: 1–13.CrossRefGoogle Scholar
  9. Chua KJ, Chou SK, Yang WM, Yan J (2013). Achieving better energy-efficient air conditioning — A review of technologies and strategies. Applied Energy, 104: 87–104.CrossRefGoogle Scholar
  10. Deng J, Wang RZ, Han GY (2011). A review of thermally activated cooling technologies for combined cooling, heating and power systems. Progress in Energy and Combustion Science, 37: 172–203.CrossRefGoogle Scholar
  11. Dincer I (2002). On thermal energy storage systems and applications in buildings. Energy and Buildings, 34: 377–388.CrossRefGoogle Scholar
  12. Dincer I, Rosen MA (1999). Energy, environment and sustainable development. Applied Energy, 64: 427–440.CrossRefGoogle Scholar
  13. Du JS, Fu L, Jiang Y (2003). Application of cool storage tank in district cooling system. Journal of HV & AC, 33(2): 97–99. (in Chinese)Google Scholar
  14. Duanmu L, Wang ZJ, Zhai ZJ, Li XL (2013). A simplified method to predict hourly building cooling load for urban energy planning. Energy and Buildings, 58: 281–291.CrossRefGoogle Scholar
  15. Fu JP, Wu SS (2011). The energy planning of Guangzhou University Town. Building Energy & Environment, 30(4): 42–44. (in Chinese)Google Scholar
  16. Gang WJ, Wang SW, Gao DC, Xiao F (2015). Performance assessment of district cooling systems for a new development district at planning stage. Applied Energy, 140: 33–43.CrossRefGoogle Scholar
  17. Gang WJ, Wang SW, Xiao F, Gao DC (2016). District cooling systems: Technology integration, system optimization, challenges and opportunities for applications. Renewable and Sustainable Energy Reviews, 53: 253–264.CrossRefGoogle Scholar
  18. Guo CM, Chu SL, You YW (2018). The theoretical study and field measurement of energy efficiency on district cooling system. Journal of Tianjin Chengjian University, 24(1): 62–67. (in Chinese)Google Scholar
  19. Hani A, Koiv TA (2012). The preliminary research of sea water district heating and cooling for Tallinn coastal area. Smart Grid and Renewable Energy, 3: 246–252.CrossRefGoogle Scholar
  20. Heier J, Bales C, Martin V (2015). Combining thermal energy storage with buildings—A review. Renewable and Sustainable Energy Reviews, 42: 1305–1325.CrossRefGoogle Scholar
  21. Hui RN, Xu Q, Li DY, Xu WF (2007). The existing condition and development of the district cooling system in China. Building Energy Efficiency, 35(3): 47–50. (in Chinese)Google Scholar
  22. Jiang XQ, Long WD, Li M (2010). Hourly cooling load analysis and prediction in a district cooling system. Journal of Central South University, 41(1): 357–363. (in Chinese)Google Scholar
  23. Li XL, Duanmu L, Shu HW (2010). Optimal design of district heating and cooling pipe network of seawater-source heat pump. Energy and Buildings, 42: 100–104.CrossRefGoogle Scholar
  24. Ma HQ, Long WD (2008). Energy efficiency of district cooling systems. Journal of HV & AC, 38(11): 59–64. (in Chinese)Google Scholar
  25. Ma HQ, Long WD (2009). Present status and prospects of district cooling system. Journal of HV & AC, 39(10): 52–59. (in Chinese)Google Scholar
  26. Nagota T, Shimoda Y, Mizuno M (2008). Verification of the energy-saving effect of the district heating and cooling system—Simulation of an electric-driven heat pump system. Energy and Buildings, 40: 732–741.CrossRefGoogle Scholar
  27. Okitsu J, Khamis MFi, Zakaria N, Naono K, Haruna AA (2015). Toward an architecture for integrated gas district cooling with data center control to reduce CO2 emission. Sustainable Computing: Informatics and Systems, 6: 39–47.Google Scholar
  28. Peng YH, Lian ZW, Fu HM (2011). Discussion on the energy efficiency of district cooling system based on load characteristics. Journal of Donghua University, 37(1): 109–114. (in Chinese)Google Scholar
  29. Powell KM, Cole WJ, Ekarika UF, Edgar TF (2013). Optimal chiller loading in a district cooling system with thermal energy storage. Energy, 50: 445–453.CrossRefGoogle Scholar
  30. Rosen A, Le N, Dincer I (2004). Exergetic analysis of cogeneration-based district energy systems. Proceedings of the Institution of Mechanical Engineers, Part A: Journal of Power and Energy, 218: 369–375.Google Scholar
  31. Sameti M, Haghighat F (2017). Optimization approaches in district heating and cooling thermal network. Energy and Buildings, 140: 121–130.CrossRefGoogle Scholar
  32. Seeley RS (1996). District cooling gets hot. Mechanical Engineering, 118(7): 82–84.Google Scholar
  33. Sehar F, Rahman S, Pipattanasomporn M (2012). Impacts of ice storage on electrical energy consumptions in office buildings. Energy and Buildings, 51: 255–262.CrossRefGoogle Scholar
  34. Seo BM, Lee KH (2016). Detailed analysis on part load ratio characteristics and cooling energy saving of chiller staging in an office building. Energy and Buildings, 119: 309–322.CrossRefGoogle Scholar
  35. Shimoda Y, Nagota T, Isayama N, Mizuno M (2008). Verification of energy efficiency of district heating and cooling system by simulation considering design and operation parameters. Building and Environment, 43: 569–577.CrossRefGoogle Scholar
  36. Wu XQ, Chen ZQ (2017). Performance analysis of a district cooling system based on operation data. Procedia Engineering, 205: 3117–3122.CrossRefGoogle Scholar
  37. Xiao HQ (2009). Study on optimal analysis of district cooling system of high-rise residential area in Nanjing. Master Thesis, Nanjing University of Science and Technology, China. (in Chinese)Google Scholar
  38. Yau YH, Rismanchi B (2012). A review on cool thermal storage technologies and operating strategies. Renewable and Sustainable Energy Reviews, 16: 787–797.CrossRefGoogle Scholar
  39. Yin P (2013). Research of combined cooling heating and power systems (4): District cooling and heating. Journal of HV & AC, 43(7): 10–17. (in Chinese)Google Scholar
  40. Yu FW, Chan KT (2007). Optimum load sharing strategy for multiple-chiller systems serving air-conditioned buildings. Building and Environment, 42: 1581–1593.CrossRefGoogle Scholar
  41. Zhu YX, Wang G, Jiang Y (2008). Energy consumption analysis of district cooling systems. Journal of HV & AC, 38(1): 36–40. (in Chinese)Google Scholar

Copyright information

© Tsinghua University Press and Springer-Verlag GmbH Germany, part of Springer Nature 2019

Authors and Affiliations

  • Lun Zhang
    • 1
    Email author
  • Jun Jing
    • 1
  • Mengfan Duan
    • 2
  • Mingyang Qian
    • 2
  • Da Yan
    • 2
  • Xiaosong Zhang
    • 1
  1. 1.School of Energy and EnvironmentSoutheast UniversityNanjingChina
  2. 2.Department of Building Science, School of ArchitectureTsinghua UniversityBeijingChina

Personalised recommendations