Abstract
Sewage source heat pump unit operates under partial load most of the time, and study on the law of coefficient of performance (COP) of the unit varying with load ratio can provide basis for the heat pump units running in high efficiency. A mathematical model determining COP, evaporation temperature and condensation temperature of a single unit was proposed. Under the condition of uniform load distribution, the model was established according to different ways of bearing partial load with the same type multiple units but different parallel operation models, and the operation characteristics of units were analyzed as well. Results show that the single screw water-source heat pump can maintain high COP only at 60%–100% load ratio, COP decreases sharply with the decrease of load ratio, and the units with parallel operation are controlled by the load ratio of a single unit according to the reduction of total load which can keep the average COP at high level within a wide load range.
Similar content being viewed by others
References
Lindström H O. Experiences with a 3.3 MW heat pump using sewage water as heat source[J]. Journal of Heat Recovery Systems, 1985, 5(1): 33–38.
CADDET (The Centre for the Analysis and Dissemination of Demonstrated Energy Technologies) Energy Efficiency. First DHC System in Japan Using Untreated Sewage as a Heat Source[R]. Result 290, JP97. 503/5X. D01, 1997, 112–125.
Arashi Norio, Inaba Atsushi. Evaluation of energy use in district heating and cooling plant using sewage and one using air as heat source[J]. Journal of the Japan Institute of Energy, 2000, 79(5): 446–454.
Yoshi T. Technology for utilizing unused low temperature difference energy[J]. Journal of the Japan Institute of Energy, 2001, 80(8): 696–706.
Funamizu N, Iida M, Sakakura Y. Reuse of heat energy in waste water: Implementation examples in Japan[J]. Water Science and Technology, 2001, 43(10): 277–286.
Ma Zuiliang, Yao Yang, Zhao Liying. Prospect of the application of sewage heat pump system[J]. China Water & Wastewater, 2003, 19(7): 41–43 (in Chinese).
Wu Ronghua, Sun Dexing, Zhang Chenghu et al. Application and progress of urban wastewater as a cool and heat source[J]. Journal of Harbin Institute of Technology, 2006, 38(8): 1326–1329 (in Chinese).
Zhou Wenzhong, Li Jianxing, Tu Guangbei. Prospect of sewage source heat pump systems and cooling and heating energy utilization of sewage[J]. Journal of HVAC, 2004, 34(8): 25–29 (in Chinese).
Huang Guoqi. Development and usage of urban wastewater heat pump[J]. Fluid Machinery, 2005, 33(6): 76–78 (in Chinese).
Baek N C, Shin U C, Yoon J H. A study on the design and analysis of a heat pump heating system using wastewater as a heat source[J]. Solar Energy, 2005, 78: 427–440.
Fu Yunzhun, Lin Bao, Zhang Xu. The application of frequency conversion technology on the system of groundwater source heat pump[J]. Journal of Shenyang Jianzhu University (Natural Science), 2005, 21(3): 250–252(in Chinese).
Ye Jianfei, Lin Xiaoping, Ye Xiangcheng. Performance analysis of air-conditioning pump under a frequency conversion[ J]. Refrigeration, 2001, 20(4): 68–71(in Chinese).
Chang Yung Chung, Lin Jui Kun, Chuang Meng Hsuan. Optimal chiller loading by genetic algorithm for reducing energy consumption[J]. Energy and Buildings, 2005, 37: 147–155 (in Chinese).
Xia Guoxin, Chen Rudong. Matching of load dynamic characteristic and refrigerating unit performance[J]. Fluid Machinery, 2003, 31: 3–55 (in Chinese).
Webb R L, Pals C. Nucleate boiling data for five refrigerants on plain, integral-fin and enhanced tube geometries [J]. Int J Heat and Mass Transfer, 1992, 35(8): 1893–1904.
Browne M W, Bansal P K. Heat transfer characteristics of boiling phenomenon in flooded refrigerant evaporators [J]. Applied Thermal Engineering, 1999, 19: 595–624.
Sergio Casciaro, Tome J R. Thermal performance of flooded evaporators (Part 1): Review of boiling heat transfer studies[J]. ASHRAE Transactions, 2001, 107(1): 903–918.
Webb R L, Apparao T V V R. Performance of flooded refrigerant evaporators with enhanced tubes[J]. Heat Transfer Engineering, 1990, 11(2): 29–43.
Huang Xinghua, Wang Qijie, Wang Ruzhu. Prediction of the performance of flooded refrigerant evaporators based on a distributed parameter model[J]. Journal of Shanghai Jiaotong University, 2004, 38(7): 1164–1169 (in Chinese).
Shi Meizhong, Wang Zhongzheng. Principle and Design of the Heat Exchanger[M]. Southeast University Press, Nanjing, China, 2003(in Chinese).
Author information
Authors and Affiliations
Corresponding author
Additional information
Supported by National Natural Science Foundation of China (No. 50578048), “Heating, Gas, Ventilation and Air Conditioning” Key Laboratory Open Subject in Beijing (No. KF200710) and the Postdoctoral Researcher Science Foundation of China (No. 20090450986).
ZHUANG Zhaoyi, born in 1982, male, doctorate student.
Rights and permissions
About this article
Cite this article
Zhuang, Z., Zhang, C., Wang, H. et al. Parallel operation characteristics analysis of sewage source heat pump units in winter. Trans. Tianjin Univ. 16, 461–466 (2010). https://doi.org/10.1007/s12209-010-1441-z
Accepted:
Published:
Issue Date:
DOI: https://doi.org/10.1007/s12209-010-1441-z