Journal of Failure Analysis and Prevention

, Volume 16, Issue 5, pp 703–711 | Cite as

Feed Water Chemistry-Related Corrosion Failures in Subcritical 250 MW Coal-Fired Boiler

Case History---Peer-Reviewed
  • 177 Downloads

Abstract

This paper emphasis on the study of typical premature failure of water wall tubes of two thermal power plant boiler of same capacity (250 MW) and same operational parameter but with different boiler water chemistry. The investigation concludes on the water-side corrosion in both of the cases. One boiler is running with coordinated phosphate treatment (CPT) and another with all volatile treatment (AVT). The causes of corrosion were discovered and proposed measures for their elimination were given. Visual examination, chemical analysis of deposits, oxide scale thickness measurement, and microstructural examination were carried to ascertain the probable cause/causes of failure. From the investigation, it was finally concluded that the combination of localized high tube metal temperature and wall thinning due to under deposit corrosion led to the premature tube failure in boiler running with CPT and localized pitting corrosion in boiler running with AVT. Based on the results and discussions, a possible way to combat the corrosion was proposed.

Keywords

Boiler tube failure All volatile treatment Caustic gouging Oxygen corrosion Scale deposition 

Notes

Acknowledgments

Authors are thankful to the Director of Birla Institute of Technology (BIT)-Deoghar-India, for giving support and permission to prepare and publish this paper. The necessary funding required is also supported by the management of Birla Institute of Technology (BIT)-Deoghar-India.

References

  1. 1.
    J.B. Kitto, S.C. Stultz, Steam: Its Generation and Use, The Babcock and Wilcox Company, 41 edn. (The Babcock & Wilcox Company, Barberton, OH, 2005), pp. 40–160.Google Scholar
  2. 2.
    R.D. Port, H.M. Herro, The Nalco Guide to Boiler Failure Analysis, Nalco Chemical Company (McGraw-Hill, New York, 1991), pp. 162–200.Google Scholar
  3. 3.
    V.I. Zarembo Kritskii, V.G. Puchkov, A.A. Slobodov, Solubility of magnetite under reducing water conditions at high temperature. Atom Energiya 3, 23–34 (1988)Google Scholar
  4. 4.
    H.A. Klein, J.K. Rice, Research study on internal corrosion of high pressure boilers. J. Eng. Power 7, 232–242 (1966)CrossRefGoogle Scholar
  5. 5.
    P. Goldstein, C.L. Burton, A research study on internal corrosion of high pressure boilers, final report. J. Eng. Power 4, 74–101 (1969)Google Scholar
  6. 6.
    I. Chattoraj, S.K. Das, B. Ravikumar, D.K. Bhattacharya, Corrosive degradation and failure of vertical furnace wall tubes of a boiler. Eng. Fail. Anal. 4(4), 279–286 (1997)CrossRefGoogle Scholar
  7. 7.
    M. Imran, Effect of corrosion on heat transfer through boiler tube and estimating overheating. Int. J. Adv. Mech. Eng. 4(6), 629–638 (2014)Google Scholar
  8. 8.
    A.U. Malik, I. Andijani, M. Mobin, F. Al-Muaili, M. Al-Hajri. Corrosion of boiler tubes-some case studies, in Proceeding of 4th SWCC Acquired Experience Symposium held at Jeddah, 2005, pp. 739–763.Google Scholar
  9. 9.
    M.A. Sohail, A.I. Mustafa, Acid cleaning operation for a natural circulation high pressure drum boiler unit of a thermal power station. Indian J. Chem. Technol. 8, 223–226 (2001)Google Scholar
  10. 10.
    S.R. Bamrotwar, V.S. Deshpande, Failures in 210 MW thermal power plant. IOSR J. Mech. Civil Eng. 2, 6–10 (2014)Google Scholar
  11. 11.
    R. Riedl, J. Dahl, I. Obernberger, M. Narodoslawasky, in Proceedings of the China International Corrosion Control Conference, vol. 9, 1999, p 1–5.Google Scholar
  12. 12.
    A.U. Malik, S.A. Al-Fozan, M. Mobinand, M. Al-Hajri, Studies on the failure of economizer tubes involving acid dew-point corrosion in high pressure boilers. Int. J. Sci. Eng. Res. 4(9), 21–30 (2013)Google Scholar
  13. 13.
    R.B. Dooley, Deposition on drum boiler tube surfaces, final technical report, EPRI-Russia, 2005, pp. 123–132.Google Scholar
  14. 14.
    N.N. Mankina, B.L. Lokotov, On the mechanism of iron oxide scaling. Teploenergetika 9, 15–17 (1973)Google Scholar

Copyright information

© ASM International 2016

Authors and Affiliations

  1. 1.Department of Applied ChemistryBirla Institute of TechnologyRanchiIndia
  2. 2.Department of Mathematical Modelling and SimulationCSIR-National Metallurgical LaboratoryJamshedpurIndia

Personalised recommendations