Advertisement

Electric Field Characteristics of an Arc-Induction-Type DC Circuit Breaker Combined with a Magnet for Stability in the DC Power Grid

  • Sang-Yong Park
  • In-Sung Jeong
  • Hye-Won Choi
  • Hui-Seok Gu
  • Hyo-Sang ChoiEmail author
Original Paper
  • 19 Downloads

Abstract

For stability in the direct current (DC) power grid, it is very important to limit the current of the fault section and to protect the system in the fault condition. That is the core technology of the DC power grid. This paper suggests characteristics and a limited range of the fault current for the new model as the significant protecting technology in the DC power grid. Such new model is the arc-induction-type DC circuit breaker (CB) combined with a magnet. The magnetic arc-induction-type direct-current circuit breaker (DCCB) consists of a neodymium magnet, an induction needle, and electrical contacts. During fault operation, the arc occurring between the contacts is induced to the induction needle. To increase the induction effect, Lorentz force is applied to blow the arc. A magnet was applied to reduce the initial fault current and to induce magnetic flux. The simulation data were analyzed using the Maxwell 3D software program. The electric field included the electric force and the electric charge. Therefore, it could analyze the arc as the electric field. The simulation was performed based on the preceding study on induction needle. As a result of the simulation, it was confirmed that the electric field value of the induction needle increased when the DCCB was combined with a magnet.

Keywords

Direct-current circuit breaker (DCCB) The arc-induction type Magnetic arc-induction type Induction needle Neodymium magnet 

Notes

Acknowledgments

This work was supported by the National Research Foundation of Korea(NRF) grant funded by the Korea government (MSIT) (No. 2018R1A2B2004242).

References

  1. 1.
    Uriarte, F.M., Gattozzi, A.L., Herbst, J.D., Estes, H.B., Estes, T.J., Kwasinski, A., Hebner, R.E.: A DC arc model for series faults in low voltage microgrids. IEEE Trans. Smart Grid. 3(4), 2063–2070 (2012)CrossRefGoogle Scholar
  2. 2.
    Kim, H.S.: Arcing characteristics on low-voltage DC circuit breakers. In: IEEE EPE Conf, France, pp. 1–7 (2013)Google Scholar
  3. 3.
    Ganhao, Z.: Study on DC circuit breaker. In: 5th International Conference on Intelligent Systems Designs and Engineering Applications (ISDEA), Human, China, pp. 942–945 (2014)Google Scholar
  4. 4.
    He, Z., Hu, J., Lin, L., Zeng, R.: Mechanical DC circuit breakers and FBSM-based MMCs in a high-voltage MTDC network: coordinated operation for network riding through DC fault. In: International Conference on RPG 2015, pp. 1–6 (2015)Google Scholar
  5. 5.
    Lee, H.Y., Lee, J.G., Khan, U.A., Lee, B.W.: Electromagnetic field analysis of low voltage DC circuit breaker for the enhancement of arc driving force. Condition monitoring and diagnosis (CMD), China, pp. 697–700, 25–28 Sept 2016 (2016)Google Scholar
  6. 6.
    IEC 60947-2 Ed.40: Low-voltage switchgear and controlgear—part 2: circuit-breakers. ANSI (2006)Google Scholar
  7. 7.
    C37.14-2002: IEEE standard for low-voltage DC power circuit breakers used in enclosures. IEEE (2002)Google Scholar