Air Curtains Combined with Smoke Exhaust for Smoke Control in Case of Fire: Full-Size Experiments

  • João Carlos Viegas
  • Hildebrando Cruz
Article
  • 68 Downloads

Abstract

This paper analyses the possibility of using air curtains to prevent smoke flow from fire compartments. Full size experiments have been carried out and several relevant conditions to assess smoke-tightness have been tested. The smoke temperature during the tests was ranging from 182°C to 351°C, the angle measured between the curtain axis and the vertical plane was ranging from 18° and 26°, the nozzle thickness was ranging from 0.017 m to 0.045 m and the velocity at the nozzle was ranging from 8.3 m/s to 19.9 m/s. During the tests, the air curtain’s nozzle was positioned horizontally at the top of a permanent opening (door). With this configuration, we obtained an approximately vertical downward jet through the used opening. This paper includes the final results of the tests and develops an analytical tool for predicting the performance of air curtains. It was concluded that it is possible to achieve smoke-tightness, provided that the adequate plane jet parameters and the compartment’s smoke exhaust are correctly adjusted. According to this analysis, the smoke-tightness limit corresponds to equation \( B = \Delta {\text{P}}_{\text{a}} /\Delta {\text{P}}_{\text{s}} = - 0.30 \,u_{a} /u_{a\_min} + 1.25 \) (with \( 1.30 \le u_{a} /u_{a\_min} \le 1.67 \)).

Keywords

Smoke control Plane jets Full size experiments Vertical air curtains 

List of symbols

\( {\text{b}}_{0} \)

Thickness of the jet nozzle (the smallest side of the rectangular shaped nozzle)

\( {\text{B}} \)

Non-dimensional proportionality value assessed by experiments

\( C \)

Non-dimensional proportionality value assessed by experiments

\( \overline{{{\text{C}}_{\text{p}} }} \)

Average specific heat at constant pressure

\( {\text{C}}_{{{\text{p}}0}} \)

Specific heat at constant pressure at temperature \( {\text{T}}_{0} \)

\( {\text{C}}_{{{\text{p}}1}} \)

Specific heat at constant pressure at temperature T1

\( {\text{D}}_{\text{m}} \)

Deflection modulus

g

Gravity acceleration

h

Soffit height above the neutral plane

H

Full height of the door

\( {\dot{\text{m}}} \)

Mass flow rate in the plume at height z

\( {\dot{\text{M}}}_{{\text{exaust}}} \)

Exhaust mass flow rate

\( \dot{Q}^{{}} \)

Heat release rate

\( {\dot{\text{Q}}}_{\text{c}} \)

Exhaust convective part of the heat release rate

\( {\text{T}}_{0} \)

Initial temperature

T1

Smoke temperature

\( {\bar{\text{T}}}_{\text{smoke}} \)

Measured smoke temperature

\( {\text{u}}_{\text{a}}^{{}} \)

Average horizontal component of the velocity through the door

\( {\text{u}}_{{{\text{a}}\_{ \hbox{min} }}} \)

Minimum average velocity at the door given by Eq. (7)

\( {\text{u}}_{0}^{{}} \)

Initial jet velocity

\( U\left( {\dot{Q}} \right) \)

Standard uncertainty of heat release rate

\( {\dot{\text{V}}}_{\text{door}} \)

Volume flow rate at the door

\( {\dot{\text{V}}}_{{\text{exaust}}} \)

Exhaust volume flow rate

\( {\dot{\text{V}}}_{\text{jet}} \)

Volume flow rate of the plane jet

w

Door width

x

Length of the jet

z

Interface height

\( {\text{z}}_{1} \)

Flame height

\( \propto_{0} \)

Angle measured between the curtain axis and the vertical plane

\( \Delta {\text{P}}_{\text{s}} \)

Pressure difference due to the difference in fluid density between the interior and exterior

\( \Delta {\text{P}}_{\text{a}} \)

Pressure difference due to momentum

\( \uprho_{0} \)

Outdoor density

\( \uprho_{1} \)

Indoor density

\( {\bar{\rho }}_{\text{smoke}} \)

Average smoke density

Notes

Acknowledgments

This research was partially funded by ADI – Agência de Inovação, under Grant QREN no. 23226 (Smoke Shield), through Operational Competitiveness Programme (COMPETE), as part of the National Strategic Reference Framework.

References

  1. 1.
    Gupta S, Pavageau M, Elicer-Cortés JC (2007) Cellular confinement of tunnel sections between two air curtains. Build Environ 42:3352–3365CrossRefGoogle Scholar
  2. 2.
    Sakurai H, Hayashi T, Shibata M, Kanehara K (1979/80) Researches on air shutter for fire defence. Fire Safety J 2:9–16Google Scholar
  3. 3.
    Cumo F, Rossetti S, Guidi G (2000) 3D simulation of dynamic barriers against fume and gaseous toxic substances. In: Proceedings of the ventilation 2000—6th international symposium on ventilation for contaminant control, 4–7 June, Helsinki, FinlandGoogle Scholar
  4. 4.
    Dufresne de Virel M, Solliec C, Guyonnaud L (1998) Mise en sécurité contre fumées d’incendie. Revue Face au Risque 348:13–18Google Scholar
  5. 5.
    Altinakar MS, Weatherill A (2001) Use of an inclined air curtain for preventing smoke propagation in a tunnel during fire emergency. In: Proceedings of the 4th international conference on safety in road and rail tunnelsGoogle Scholar
  6. 6.
    Gugliermetti F, Santarpia L, Zori G (2003) Air curtain applied to fire smoke pollution control, air pollution 2003. In: 11th international conference on modelling, monitoring and management of air pollution, September 17–19, Catania, Italy, pp 541–549Google Scholar
  7. 7.
    Sawley M, Greveldinger B, Drotz A (2004) Numerical flow simulation of an air curtain for road tunnel fire safety. Supercomput Rev 14:3–6Google Scholar
  8. 8.
    Hu LH, Zhou JW, Huo R, Peng W, Wang HB (2008) Confinement of fire-induced smoke and carbon monoxide transportation by air curtain in channels. J Hazard Mater 156:327–334CrossRefGoogle Scholar
  9. 9.
    Felis F, Pavageau M, Elicer-Cortés JC, Dassonville T (2010) Simultaneous measurements of temperature and velocity fluctuations in a double stream-twin jet air curtain for heat confinement in case of tunnel fire. Int Commun Heat Mass Transfer 37:1191–1196CrossRefGoogle Scholar
  10. 10.
    Yp I, Chiu YL, Wu SJ (2009) The simulation of air recirculation and fire/explosion phenomena within a semiconductor factory. J Hazard Mater 163:1040–1051CrossRefGoogle Scholar
  11. 11.
    Shih Y-C, Yang A-S, Lu C-W (2011) Using air curtain to control pollutant spreading for emergency management in a cleanroom. Build Environ 46:1104–1114CrossRefGoogle Scholar
  12. 12.
    Luo N, Li A, Gao R, Zhang W, Tian Z (2013) An experiment and simulation of smoke confinement utilizing an air curtain. Saf Sci 59:10–18CrossRefGoogle Scholar
  13. 13.
    Viegas J, Cruz H (2014) Saltwater experiments of air curtains for smoke control in fires. V Conferência Nacional de Mecânica dos Fluidos, Termodinâmica e Energia—MEFTE 2014, 11–12 Setembro 2014, Porto, PortugalGoogle Scholar
  14. 14.
    Viegas J, Cruz H (2014) Computational simulation on the performance of air plane jets for smoke control. 4. as Jornadas de Segurança aos Incêndios Urbanos, 6–7 novembro de 2014, Bragança, PortugalGoogle Scholar
  15. 15.
    Viegas J, Cruz H (2015) Full-size experiments of air curtains for smoke control in case of fire. In: IFireSS—international fire safety symposium, 20th–23rd April 2015, Coimbra, PortugalGoogle Scholar
  16. 16.
    Viegas JC (2016) Saltwater experiments with air curtains for smoke control in the event of fire. J Build Eng 8:243–248CrossRefGoogle Scholar
  17. 17.
    NFPA 204—Standard for Smoke and Heat VentingGoogle Scholar
  18. 18.
    JCGM 100:2008—evaluation of measurement data—guide to the expression of uncertainty in measurement. Joint Committee for Guides in MetrologyGoogle Scholar