, Volume 135, Issue 8, pp 567–575 | Cite as

New single-ended earthfault distance estimation for the 110-kV- and 20-kV-compensated network

  • Gernot Druml
  • Georg Achleitner
  • Wolfgang Leitner
  • Lothar Fickert
CIGRE 2018
  • 20 Downloads

Abstract

Due to today´s increased demands on grid operation management, new methods for earth fault localization and detection are needed. The fault localization should be performed as quickly as possible and under the condition, that the fault current at the fault location will not be significantly increased.

The pros and cons of Distance Protection in solid grounded networks are well known. In case of a single-line earthfault, the current via the fault location in solid grounded networks is in the range of some kA. In compensated networks the residual current \(I_{\mathrm{res}}\) via the fault location is, in case of a single line fault, only few ampere. Very often this current is much smaller than the load current of the feeder. A distinction between load current, circulating currents in meshed networks and fault current is more or less not possible. Therefore, the Earthfault-Distance-Protection in compensated networks is usually switched off.

With the new transient relays, based on the qu2-algorithm, it is possible to detect in the substation very reliable the faulty feeder and the direction of the fault. This statement is also correct for meshed networks. In a 110-kV-network the distance between two substations is in the range of 50 km to 200 km. Also if the feeder is identified correctly, it is still a challenge to locate the exact fault position on this feeder.

The results of field-test in a 110-kV-network with different fault impedances will be presented.

Keywords

Fault location Two-end data algorithm Simulation tool 

References

  1. 1.
    Aichhorn, A., Etzlinger, B., Mayrhofer, R., Springer, A. (2016): Accurate clock synchronization for power systems protection devices over packet switched networks. Comput. Sci. Res. Dev., 32(1–2), 147,–158. 2017. Google Scholar
  2. 2.
    Achleitner, G. (2008): Earth fault distance protection. Dissertation, Technische Universtität Graz. Google Scholar
  3. 3.
    Achleitner, G., Leitner, W., Druml, G., Simon, R., Fickert, L. (2017): 110-kV-Erdschlussversuch und Test eines Erdschlussdistanzschutzes. In Proccedings ETG Fachtagung STE 2017 Aschaffenburg. ETG-Fachbericht (Vol. 151). Berlin: VDE-Verlag. Google Scholar
  4. 4.
    Druml, G. (2013): Innovative Methoden zur Erdschlussortung und Petersen-Spulen Regelung. Thesis, Institute of Electrical Power System in Graz, Austria. Google Scholar
  5. 5.
    Druml, G., Schmidt, U., Schegner, P. (2016): Effects of the nonlinear Arc of a 20-kV-net single-line cable fault on the earth-fault-detection and control. In Conference PAC world 2016, Ljubljana, Slovenia. Google Scholar
  6. 6.
    Druml, G., Seifert, O., Zickler, U., Roser, M., Fickert, L. (2011): Auswertung von nichtlinearen Erdschlüssen. In Proccedings ETG Fachtagung STE 2011 Erfurt. ETG-Fachbericht (Vol. 129). Berlin: VDE-Verlag. Google Scholar
  7. 7.
    Druml, G., Skrbinjek, O., Hipp, W., Aichhorn, A., Schmidt, U., Schegner, P. (2017): Abschätzung der Fehlerentfernung von Erdschlüssen basierend auf Wanderwellen. In Proccedings ETG Fachtagung STE 2017 Aschaffenburg. ETG-Fachbericht (Vol. 151). Berlin: VDE-Verlag. Google Scholar
  8. 8.
    Herold, G. (2008): Elektrische Energieversorgung II. Weil der Stadt: Schlembach Fachverlag. Google Scholar
  9. 9.
    Imriš, P. (2008): Transient based earth fault localisation in 110 kV subtransmission networks. TKK dissertation, Espoo, Finland. Google Scholar
  10. 10.
    Küchler, A. (2009): Hochspannungstechnik, Grundlagen-Technologie-Anwendungen. 3rd. ed. Berlin: Springer. Google Scholar
  11. 11.
    Melzer, H. (2012): Die aktuelle Situation der Sternpunktbehandlung in Netzen bis 110 kV (D-A-CH). In ETG-Fachbericht (Vol. 132). Berlin: VDE. 2012. Google Scholar
  12. 12.
    Tengg, Ch., Schoass, K., Druml, G., Schmaranz, R., Marketz, M., Fickert, L. (2013): Evaluation of new earth fault localization methods by earth fault experiments. In CIRED Stockholm (p. 1317). Google Scholar
  13. 13.
    Wurm, M. (2013): Vergleich der Bestimmungsmethoden der Fehlerortentfernung beim einpoligen Fehler und Nachweis im praktischen Netzbetrieb. Dissertation, Technische Universtität Graz. Google Scholar

Copyright information

© CIGRE - Reprint from www.cigre.org with kind permission 2018

Authors and Affiliations

  • Gernot Druml
    • 1
  • Georg Achleitner
    • 2
  • Wolfgang Leitner
    • 3
  • Lothar Fickert
    • 4
  1. 1.Sprecher Automation GmbHLinzAustria
  2. 2.Austrian Power Grid AGViennaAustria
  3. 3.Netz Oberösterreich GmbHGmundenAustria
  4. 4.Graz University of TechnologyGrazAustria

Personalised recommendations